COS-2 /24V
- Herstellernummer
- EAN
Bestellung
- Bestelleinheit
- Stück
Beschreibung
Relay monitors phase shift between current and voltage - cos-? in 3-phase and also 1-phase DESCRIPTION • Relay monitors phase shift between current and voltage in 3-phase or 1-phase networks - evaluates COS ? (replacement COS-1) • The relay is designed to monitor overload / relieve the motors • Relay is designed for 3 x 400 / 230V circuits • Galvanically isolated power supply AC 230V, AC 110V, AC 400V or AC / DC 24V • Adjustable upper and lower level COS ? • Possibility to extend the current range using a current transformer • Adjustable MEMORY function • Two output relays (for each level independent) • Adjustable delay eliminating engine start-up • Output contact 2x changeover 16A / 250V AC1 • 3-MODULE design, mounting onto DIN rail.
Technische Daten
ETIM-Klasse: Wirkleistungsüberwachungsgerät (EC001443)
Connection
- Ausführung des elektrischen Anschlusses
- Klammeranschluss
- Anzahl der Kontakte als Öffner
- 0
- Anzahl der Kontakte als Schließer
- 0
- Anzahl der Kontakte als Wechsler
- 2
Electrical
- Bemessungssteuerspeisespannung Us bei AC 50 Hz
- 24, 24
- Bemessungssteuerspeisespannung Us bei AC 60 Hz
- 24, 24
- Bemessungssteuerspeisespannung Us bei DC
- 24, 24
- Spannungsart zur Betätigung
- AC/DC
- Bemessungsspannung
- 24, 24
- Anzahl der Phasen
- 3
Model/type
- Mit abnehmbaren Klemmen
- Nein
- Messstrom
- 0.1, 16
Other
- Bemessungsbetriebsfrequenz
- 50, 60 Hz
Setting/control
- Einstellbarer Ansprechwert für Cos-Phi
- 0.1, 0.99
- Min. einstellbare Ansprechverzögerungszeit
- 0.5 s
- Min. einstellbare Rückfallverzögerungszeit
- 0 s
Operating conditions
- Max. zulässige Ansprechverzögerungszeit
- 30 s
- Max. zulässige Rückfallverzögerungszeit
- 10 s
Measurements
- Breite
- 52 mm
- Höhe
- 90 mm
- Tiefe
- 65 mm