Photo 1 of 3
MS132-0.4KT Circuit-breaker for primary
- Manufacturer part no.
- EAN
- Series
- MS132
Ordering
- Order unit
- piece
Description
The circuit breaker for transformer protection MS132-0.4KT is a compact 45 mm width device designed to protect control transformers on the primary side. This device has a rated operational current of Ie = 0.4 A with Push-In Spring terminals. It allows fuseless protection against overload and short-circuit. The short-circuit current setting is fixed to 20 times the rated operational current to handle the high inrush current generated by transformers. The device allows manually connect and disconnect the transformer from the mains thanks of its built-in disconnection function. The circuit breaker for transformer protection offers a rated service short-circuit breaking capacity of Ics = 100 kA at 400 VAC and trip class 10. Further features are temperature compensation, trip-free mechanism, rotary handle with a clear switch position indication and short circuit trip indicator. The handle is lockable to protect against unauthorized changes. Auxiliary contacts, signalling contacts, undervoltage releases, shunt trips and terminal spacers are available as accessory.
Tender text
Transformatorschutzschalter MS132-KT in schraubenloser Push-in Federanschlusstechnik mit thermischem und elektromagnetischem Schutz mit hohem Kurzschlussausschaltzvermögen für Transformatoren mit Primärstömen bis 25 A gemäß IEC/EN60947-1, -2, -4-1. UL-Zulassung als "Motor controller" für Sonderanwendung Transformatorschutz erlaubt Einsatz in Nordamerika. Der primärseitige Transformatornennstrom wird durch Einstellen an der Stromskala thermisch überwacht. Die Kurzschlussauslösung erfolgt bei Auftreten des 20-fachen Gerätenennstroms. Das temperaturkompensierte Gerät besitzt eine Modulbreite von 45 mm, wird mithilfe eines direkt abschließbaren Drehgriffes mit einer klaren Schaltstellungsanzeige (I/TRIP/0) bedient und verfügt über eine Kurzschlussanzeige. Die Push-in Federanschlussklemmen erlauben für starre Drähte und Litzen mit Aderendhülsen werkzeugloses und zeitsparendes Einstecken der Anschlussleitungen, Litzen ohne Aderendhülsen können ebenfalls angeschlossen werden; ein späteres Nachjustieren der Anschlüsse entfällt. Push-in Feder Varianten gibt es für Hilfs- und Signalkontakte, diese passen auch an die Transformatorschutzschalter in Schraubtechnik. Normen: IEC/EN 60947-1, IEC/EN 60947-2, IEC/EN 60947-4-1, IEC 60335-2-40 A2L Anzahl Pole: 3P Bemessungsausschaltvermögen Im, Bemessungsfehlerschaltvermögen IΔm: 100 kA, 100 kA Bemessungsbetriebsspannung: 690 V AC Bemessungsdauerstrom: 0.4 A Bemessungsisolationsspannung: 690 V Bemessungsstoßspannungsfestigkeit: 6 kV
Technical data
ETIM class: Power circuit-breaker for trafo/generator/installation protection (EC000228)
Electrical
- Rated permanent current Iu
- 0.4 A
- Rated voltage
- 690, 690 V
- Rated short-circuit breaking capacity Icu at 400 V, 50 Hz
- 100 kA
- Overload release current setting
- 0.25, 0.40 A
- Adjustment range short-term delayed short-circuit release
- NA, - A
- Adjustment range undelayed short-circuit release
- 8, 8 A
- Power loss
- 4.5 W
- With integrated under voltage release
- -
- Number of poles
- 3
Other
- Device construction
- Complete device in housing
Protection
- Integrated earth fault protection
- No
- Complete device with protection unit
- Yes
- Degree of protection (IP)
- IP20
Connection
- Type of electrical connection of main circuit
- Spring clamp connection
- Number of auxiliary contacts as normally closed contact
- 0
- Number of auxiliary contacts as normally open contact
- 0
- Number of auxiliary contacts as change-over contact
- 0
- Position of connection for main current circuit
- Front side
Mounting/installation
- Suitable for DIN rail (top hat rail) mounting
- Yes
- DIN rail (top hat rail) mounting optional
- Yes
Model/type
- With switched-off indicator
- Yes
- Type of control element
- Turn button
- Motor drive integrated
- No
Options
- Motor drive optional
- No
Logistics
- Net weight
- 0.256 kg
- Country of origin
- Germany
- Customs tariff number
- 85362010
Packaging
| Pack | Quantity | GTIN | Gross weight | Dimensions (L × W × D) |
|---|---|---|---|---|
| BE | 0 | — | — | — |