Photo 1 of 3
MS132-25L Lamp Circuit Breaker
- Manufacturer part no.
- EAN
- Series
- MS132
Ordering
- Order unit
- piece
Description
The MS132-25L lamp circuit breaker is a compact 45 mm width device with a rated operational current of Ie = 25.0 A. This device is used to manually switch on and off lamp loads (and loads with similar characteristics) and to protect them reliably and without the need for a fuse from short-circuits, overload and phase failures. The lamp circuit breaker offers a rated service short-circuit breaking capacity Ics = 50 kA at 400 VAC. Further features are the build-in disconnect function, temperature compensation, trip-free mechanism and a rotary handle with a clear switch position indication. The lamp circuit breaker is suitable for three- and single-phase applications. The handle is lockable to protect against unauthorized changes. Auxiliary contacts, signaling contacts, undervoltage releases, shunt trips, 3-phase bus bars, power in-feed blocks and terminal spacers are available as accessory.
Tender text
Der MS132-25L ist ein Lampenstarter mit einem Stromeinstellbereich von 20..25A. Er dient als Schalt- und Schutzorgan für Lampenlasten in beispielsweise Gewächshäusern. Der MS132-20L ist ein Lampenstarter mit einem Stromeinstellbereich von 16..20A. Er dient als Schalt- und Schutzorgan für Lampenlasten in beispielsweise Gewächshäusern. Die magnetische Auslösung erfolgt bei diesem Gerät bei 15 x In (+/-20%) im Falle eines Kurzschlusses. Außerdem verfügt der Lampenstarter über die Auslöseklasse 10 und kann mit dem Standard-MS132 Zubehör ausgestattet werden. Des weiteren lassen sich Direkt-Starterkombinationen aus MS132-xxL und AFxx-L Lampenlastschützen realisieren. Außerdem verfügt der Lampenstarter über die Auslöseklasse 10 und kann mit dem Standard-MS132 Zubehör ausgestattet werden. Des weiteren lassen sich Direkt-Starterkombinationen aus MS132-xxL und AFxx-L Lampenlastschützen realisieren. Normen: IEC/EN 60947-1, IEC/EN 60947-2, IEC 60335-2-40 A2L Anzahl Pole: 3P Bedienteilausführung: Drehgriff Bemessungsausschaltvermögen Im, Bemessungsfehlerschaltvermögen IΔm: 50 kA, 10 kA, 50 kA, 30 kA, 10 kA, 3 kA Bemessungs-Grenzkurzschlussausschaltvermögen: 50 kA, 50 kA, 30 kA, 10 kA, 3 kA Bemessungsauslösestrom der unverzögerten Auslösung: 375 A Bemessungsbetriebsleistung AC-3: 11 kW Bemessungsbetriebsspannung: 690 V AC, 250 V DC Bemessungsbetriebsstrom AC-3: 25 A Bemessungsstoßspannungsfestigkeit: 6 kV Einstellbereich: 20 ... 25 A Schutzart: IP20, IP10
Technical data
ETIM class: Motor protection circuit-breaker (EC000074)
Electrical
- Overload release current setting
- 20, 25 A
- Adjustment range undelayed short-circuit release
- 375, 375 A
- Rated operating voltage
- 250, 690 V
- Rated permanent current Iu
- 25 A
- Rated operation power at AC-3, 230 V
- 11 kW
- Rated operation power at AC-3, 400 V
- 11 kW
- Power loss
- 8.4 W
- With integrated under voltage release
- No
- Number of poles
- 3
- Rated short-circuit breaking capacity Icu at 400 V, AC
- 50 kA
Model/type
- With thermal overload protection
- Yes
- Type of control element
- Turn button
- With integrated auxiliary switch
- No
Options
- Phase failure sensitive
- Yes
Other
- Switch off technique
- Thermomagnetic
- Device construction
- Complete device in housing
Connection
- Type of electrical connection of main circuit
- -
Protection
- Degree of protection (IP)
- IP20
Measurements
- Height
- 97.8 mm
- Height
- 3.850386 inch
- Width
- 45 mm
- Width
- 1.77165 inch
- Depth
- 87 mm
- Depth
- 3.42519 inch
Logistics
- Net weight
- 0.31 kg
- Country of origin
- Germany
- Customs tariff number
- 85362010
Packaging
| Pack | Quantity | GTIN | Gross weight | Dimensions (L × W × D) |
|---|---|---|---|---|
| BE | 0 | — | — | — |