Description
MS165 is a compact and powerful range for motor protection up to 45 kW (400 V) / 80 A in width of 55 mm. They offer a reliable protection for motors in the event of overload or phase failure. The devices have trip class 10. This type has also a clear and reliable indication of fault in a separate window in the event of short-circuit tripping. Further features are the build-in disconnect function, temperature compensation, trip-free mechanism and a rotary handle with a clear switch position indication. The manual motor starter (also known as motor protection circuit breaker or manual motor protector) is suitable for three- and single phase applications. The handle is lockable to protect against unauthorized changes. Auxiliary contacts, signaling contacts, undervoltage releases, shunt trips, power in-feed blocks are available as accessory. These are suitable throughout the MS116/MS132/MS165 range.
Tender text
Motorschutzschalter MS165 mit thermischem und elektromagnetischem Schutz steht für die kompakte und leistungsstarke Baureihe mit hohem Kurzschlussausschaltvermögen für den Motorschutz bis 45 kW (400 V) mit einer Modulbreite von 55 mm. Das temperaturkompensierte Gerät hat eine Drehgriffbedienung mit einer klaren Schaltstellungsanzeige I/TRIP/0. Darüber hinaus verfügt MS165 über eine Kurzschlussanzeige. Der Drehgriff ist mit Hilfe eines Vorhängeschlosses in 0-Position direkt verriegelbar. Hilfs-, Signal- und Kurschlussmeldekontakte sowie Unterspannungs- und Arbeitsstromauslöser können ohne Werkzeug angebaut werden. 3-Phasen-Schienen für 125 A erlauben die gemeinsame Einspeisung mehrerer Motorschutzschalter. Zubehör für Schaltschrankeinbau ergänzt das Sortiment. Atex-Zertifizierung erlaubt den Schutz von Motoren im Ex-Bereich, UL-Zulassung als >Self protected combination motor cotroller<erweitert den Einsatzbereich in Nordamerika. Normen: CSA 22.2 No. 14, IEC/EN 60947-1, IEC/EN 60947-2, IEC/EN 60947-4-1, UL 60947-4-1 Anzahl Pole: 3P Bedienteilausführung: Drehgriff Bemessungsausschaltvermögen Im, Bemessungsfehlerschaltvermögen IΔm: 100 kA, 100 kA, 100 kA, 50 kA, 30 kA, 10 kA Bemessungs-Grenzkurzschlussausschaltvermögen: 100 kA, 100 kA, 100 kA, 50 kA, 30 kA, 10 kA Bemessungsauslösestrom der unverzögerten Auslösung: 480 A Bemessungsbetriebsleistung AC-3: 15 kW Bemessungsbetriebsspannung: 690 V AC, 250 V DC Bemessungsbetriebsstrom AC-3: 32 A Bemessungsstoßspannungsfestigkeit: 8 kV Einstellbereich: 23 ... 32 A Schutzart: IP20, IP10
Technical data
ETIM class: Motor protection circuit-breaker (EC000074)
Electrical
- Overload release current setting
- 23, 32 A
- Adjustment range undelayed short-circuit release
- 480, 480 A
- Rated operating voltage
- 250, 690 V
- Rated permanent current Iu
- 32 A
- Rated operation power at AC-3, 230 V
- 15 kW
- Rated operation power at AC-3, 400 V
- 15 kW
- Power loss
- 13.20 W
- With integrated under voltage release
- No
- Number of poles
- 3
- Rated short-circuit breaking capacity Icu at 400 V, AC
- 100 kA
Model/type
- With thermal overload protection
- Yes
- Type of control element
- Turn button
- With integrated auxiliary switch
- No
Options
- Phase failure sensitive
- Yes
Other
- Switch off technique
- Thermomagnetic
- Device construction
- Complete device in housing
Connection
- Type of electrical connection of main circuit
- -
Protection
- Degree of protection (IP)
- IP20
Measurements
- Height
- 142.65 mm
- Height
- 5.6161305 inch
- Width
- 55 mm
- Width
- 2.16535 inch
- Depth
- 122.1 mm
- Depth
- 4.807077 inch
Logistics
- Net weight
- 0.97 kg
- Country of origin
- China
- Customs tariff number
- 85362010