Description

C.BREAKER TMAX XT2S 160 FIXED FOUR-POLE WITH FRONT TERMINALS AND THERMOMAGNETIC RELEASE TMA R 80 I3=400...800 A 50°C

Technical data

ETIM class: Power circuit-breaker for trafo/generator/installation protection (EC000228)

Electrical

Rated permanent current Iu
80 A
Rated voltage
690, 690 V
Rated short-circuit breaking capacity Icu at 400 V, 50 Hz
NA kA
Overload release current setting
56.0, 80 A
Adjustment range short-term delayed short-circuit release
NA, - A
Adjustment range undelayed short-circuit release
400, 800 A
Power loss
5.8 W
With integrated under voltage release
No
Number of poles
4

Other

Device construction
Built-in device fixed built-in technique

Protection

Integrated earth fault protection
No
Complete device with protection unit
Yes
Degree of protection (IP)
IP20

Connection

Type of electrical connection of main circuit
Bolt connection
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as change-over contact
0
Position of connection for main current circuit
Front side

Mounting/installation

Suitable for DIN rail (top hat rail) mounting
No
DIN rail (top hat rail) mounting optional
No

Model/type

With switched-off indicator
No
Type of control element
Wing knob
Motor drive integrated
No

Options

Motor drive optional
Yes

Logistics

Net weight
1.45 kg
Country of origin
Italy