Description

The AF116-30-11B-42 is a 3 pole - 690 V IEC or 600 V UL contactor with Main Circuit Bars, controlling motors up to 55 kW / 400 V AC (AC-3) or 75 hp / 480 V UL and switching power circuits up to 160 A (AC-1) or 160 A UL general use. Thanks to the AF technology, the contactor has a control voltage range (110-120 V 50/60 Hz),faster operation time, reducing panel energy consumptions and ensuring distinct operations in unstable networks. Furthermore, surge protection is built-in, offering a compact solution. AF contactors have a block type design, can be easily extended with add-on auxiliary contact blocks and an additional wide range of accessories.

Tender text

Das AF116-30-11B-42 ist ein 3-poliges 690V IEC- oder 600V UL-Schütz mit Schienenanschluss, das Mo-toren bis zu 55 kW / 400 V AC (AC-3) oder 75 hp / 480 V UL steuert und Stromkreise bis zu 160 A (AC-1) für allgemeine Anwendungen schaltet. Das Schütz besitzt einen Steuerspannungsbereich von 110-120 V 50/60 Hz und eine schnellere Anzugszeit als Standard AF-Schütze. AF-Schütze reduzieren den Energie-verbrauch der Schalttafel und realisieren einen eindeutigen Betrieb in instabilen Netzen. Außerdem ist ein werksseitiger Überspannungsschutz eingebaut. Die AF-Schütze sind in Blockbauweise ausgeführt und können leicht mit zusätzlichen Hilfskontaktblöcken und einer breiten Palette an Zubehör erweitert werden. Anschlussart: Hauptstromkreis: Schiene Anzahl Hauptkontakte Öffner: 0 Anzahl Hauptkontakte Schließer: 3 Anzahl Hilfskontakte Öffner: 1 Anzahl Hilfskontakte Schließer: 1 Typ Blockschütz: 3-poliges Schütz Bemessungsbetriebsleistung AC-3: 55 kW, 55 kW, 75 kW, 55 kW, 55 kW, 30 kW Bemessungsbetriebsspannung: 690 V Bemessungsbetriebsstrom AC-1: 160 A, 145 A, 130 A Bemessungsbetriebsstrom AC-3: 116 A, 116 A, 110 A, 65 A, 116 A, 116 A Bemessungssteuerspannung: 110 ... 120 V, 110 ... 120 V

Technical data

ETIM class: Power contactor, AC switching (EC000066)

Electrical

Rated control supply voltage AC 50 Hz
110, 120 V
Rated control supply voltage AC 60 Hz
110, 120 V
Rated control supply voltage DC
NA, - V
Voltage type for actuating
AC
Operating voltage AC 50 Hz
690, 690 V
Operating voltage AC 60 Hz
690, 690 V
Rated operation current Ie at AC-1, 400 V
160 A
Rated operation current Ie at AC-3, 400 V
116 A
Rated operation power at AC-3, 400 V
55 kW
Rated operation current Ie at AC-4, 400 V
NA A
Rated operation power at AC-4, 400 V
NA kW
Rated operation power NEMA
29.8280 kW

Connection

Number of normally closed contacts as main contact
0
Number of normally open contacts as main contact
3
Type of electrical connection of main circuit
Screw connection
Number of auxiliary contacts as normally open contact
1
Number of auxiliary contacts as normally closed contact
1

Options

Suitable for distribution board
No

Measurements

Width
90 mm
Width
3.54330 inch
Height
150 mm
Height
5.90550 inch
Depth
126 mm
Depth
4.9606326 inch

Logistics

Net weight
1.3 kg
Country of origin
Sweden
Customs tariff number
8536490099

Packaging

PackQuantityGTINGross weightDimensions (L × W × D)
BE0———