CM-UFD.M33 Grid feeding monitoring relay
- Manufacturer part no.
- EAN
- Series
- CM-UFD
Ordering
- Order unit
- piece
Description
The CM-UFD.M33 is a multi-functional grid feeding monitoring relay, which provides interface protection and is to be installed between a renewable energy system and the public grid. This innovative relay guarantees grid stability and seeks to prevent blackouts. If the voltage or frequency magnitudes of the public grid are outside the permited range, then the device changes status and acts to disconnect the renewable energy system from the public grid by sending a signal to a decoupling unit (e.g. contactor, switch disconnector or circuit breaker). As soon as the grid is stable again, the system may automatically reconnected. The CM-UFD.M33 provides different monitoring functions including over-/undervoltage and over-/underfrequency as well as rate of change of frequency (RoCoF) and vector shift monitoring functions, which detect a loss of mains event. This grid feed monitoring relay complies to G99 requirements.
Tender text
Das Netzeinspeiseüberwachungssrelais CM-UFD.M33 überwacht Spannung und Frequenz in Ein- und Dreiphasennetzen. Es erfüllt die Anforderungen der UL 508, CAN/CSA C22.2 No.14, In einem Alarmspeicher werden die letzten 99 Abschaltursachen und deren jeweiliger Zeitpunkt abgelegt. Es erfolgt außerdem eine Überwachung der angeschlossenen Kuppelschalter, Vektorsprungerkennung und eine ROCOF Frequenzgradientenüberwachung. Normen: CAN/CSA C22.2 No.14, IEC/EN 63000, IEC/EN 60255-1, IEC/EN 60255-127, IEC/EN 60255-26, IEC/EN 60255-27, IEC/EN 61000-6-2, IEC/EN 61000-6-3, IEC/EN 60255-181, UL 508, ENA EREC G98, ENA EREC G99 Anschlussart: Schraubklemme Ausgang: 3 Wechsler Bemessungsbetriebsstrom AC-15: 3 A Bemessungsbetriebsstrom DC-13: 2 A Bemessungssteuerspeisespannung: 24 ... 240 V AC/DC Breite (Netto-Abmessung): 108 mm Funktion: Über- und Unterspannungsüberwachung, unterbrochene Neutralleiterüberwachung, Über- und Unterfrequenzüberwachung, 10 min Durchschnittswertüberwachung, Vektorverschiebungserkennung, ROCOF-Überwachung Höhe (Netto-Abmessung): 90 mm Messbereich: 0 ... 550 V AC Nettogewicht: 0.304 kg Tiefe (Netto-Abmessung): 67 mm
Technical data
ETIM class: Voltage monitoring relay (EC001438)
Connection
- Type of electric connection
- Screw connection
- Number of contacts as normally closed contact
- -
- Number of contacts as normally open contact
- -
- Number of contacts as change-over contact
- -
Model/type
- With detachable clamps
- No
Electrical
- External power supply required
- Yes
- Voltage type (supply voltage)
- AC/DC
- Supply voltage AC 50 Hz
- 24, 240 V
- Supply voltage AC 60 Hz
- 24, 240 V
- Supply voltage DC
- 24, 240 V
- Voltage measuring range 1
- 0, 550 V
- Voltage measuring range 2
- 0, 550 V
- Type of voltage measuring range
- AC
- Response value voltage
- 0, 550 V
- Single-phase under voltage possible
- Yes
- Three-phase under voltage possible
- Yes
- Single-phase overvoltage possible
- Yes
- Three-phase overvoltage possible
- Yes
- Voltage type (operating voltage)
- AC/DC
- Operating voltage AC 50 Hz
- 230, 230 V
- Operating voltage AC 60 Hz
- 230, 230 V
- Operating voltage DC
- NA, - V
- Rated switch current
- 4 A
Options
- Single-phase hysteresis possible
- Yes
- Three-phase hysteresis possible
- Yes
- Contains function DC-under voltage
- No
- Contains function DC overvoltage
- No
- Contains function DC-voltage hysteresis
- No
Setting/control
- Min. adjustable delay-on energization time
- 1 s
- Min. adjustable off-delay time
- 1 s
Operating conditions
- Max. permitted delay-on energization time
- NA s
- Max. permitted off-delay time
- NA s
Measurements
- Width
- 108 mm
- Width
- 4.25196 inch
- Height
- 90 mm
- Height
- 3.54330 inch
- Depth
- 67 mm
- Depth
- 2.63779 inch
Logistics
- Net weight
- 0.304 kg
- Country of origin
- Germany
- Customs tariff number
- 85364900
Packaging
| Pack | Quantity | GTIN | Gross weight | Dimensions (L × W × D) |
|---|---|---|---|---|
| BE | 0 | — | — | — |