Skip to content
Eltracore

ABB

CM-UFD.M34M Grid feeding monitoring rel.

Manufacturer part no.
EAN
Series
CM-UFD
Guest price€1,363.68 / pcexcl. VATMinimum order 1Delivery in about 24 business days
Checking availability…
Sign in to see your personal price

Ordering

Order unit
piece

Description

The CM-UFD.M34M is a multi-functional grid feeding monitoring relay with Modbus RTU communication interface, which provides interface protection and is to be installed between a renewable energy system and the public grid. This innovative relay guarantees grid stability and seeks to prevent blackouts. If the voltage or frequency magnitudes of the public grid are outside the permited range, then the device changes status and acts to disconnect the renewable energy system from the public grid by sending a signal to a decoupling unit (e.g. contactor, switch disconnector or circuit breaker). As soon as the grid is stable again, the system may automatically reconnected. The CM-UFD.M34M provides different monitoring functions including over-/undervoltage and over-/underfrequency as well as rate of change of frequency (RoCoF) and vector shift monitoring functions, which detect a loss of mains event. This grid feed monitoring relay is certified in accordance to DEWA requirements and may be connected to the state-of-the-art cloud solution, ABB Ability Energy and Asset Manager.

Tender text

Das Netzeinspeiseüberwachungssrelais CM-UFD.M34M überwacht Spannung und Frequenz in Ein- und Dreiphasennetzen. Es erfüllt die Anforderungen des DRRG der DEWA, In einem Alarmspeicher werden die letzten 99 Abschaltursachen und deren jeweiliger Zeitpunkt abgelegt. Es erfolgt außerdem eine Überwachung der angeschlossenen Kuppelschalter, Vektorsprungerkennung und eine ROCOF Frequenzgradientenüberwachung. Integrierte Modbus RTU Kommunikationsschnittstelle. Normen: IEC/EN 63000, IEC/EN 60255-26, IEC/EN 60255-27, IEC/EN 61000-6-3, DRRG Standard (DEWA) Anschlussart: Schraubklemme Ausgang: 3 Wechsler Bemessungsbetriebsstrom AC-15: 3 A Bemessungsbetriebsstrom DC-13: 2 A Bemessungssteuerspeisespannung: 24 ... 240 V AC/DC Breite (Netto-Abmessung): 108 mm Funktion: Über- und Unterspannungsüberwachung, unterbrochene Neutralleiterüberwachung, Über- und Unterfrequenzüberwachung, 10 min Durchschnittswertüberwachung, Vektorverschiebungserkennung, ROCOF-Überwachung Höhe (Netto-Abmessung): 90 mm Messbereich: 0 ... 540 V AC Nettogewicht: 0.312 kg Tiefe (Netto-Abmessung): 67 mm

Technical data

ETIM class: Voltage monitoring relay (EC001438)

Connection

Type of electric connection
Screw connection
Number of contacts as normally closed contact
-
Number of contacts as normally open contact
-
Number of contacts as change-over contact
-

Model/type

With detachable clamps
No

Electrical

External power supply required
Yes
Voltage type (supply voltage)
AC/DC
Supply voltage AC 50 Hz
24, 240 V
Supply voltage AC 60 Hz
24, 240 V
Supply voltage DC
24, 240 V
Voltage measuring range 1
0, 540 V
Voltage measuring range 2
0, 540 V
Type of voltage measuring range
AC
Response value voltage
0, 540 V
Single-phase under voltage possible
Yes
Three-phase under voltage possible
Yes
Single-phase overvoltage possible
Yes
Three-phase overvoltage possible
Yes
Voltage type (operating voltage)
AC/DC
Operating voltage AC 50 Hz
230, 230 V
Operating voltage AC 60 Hz
230, 230 V
Operating voltage DC
NA, - V
Rated switch current
4 A

Options

Single-phase hysteresis possible
Yes
Three-phase hysteresis possible
Yes
Contains function DC-under voltage
No
Contains function DC overvoltage
No
Contains function DC-voltage hysteresis
No

Setting/control

Min. adjustable delay-on energization time
1 s
Min. adjustable off-delay time
1 s

Operating conditions

Max. permitted delay-on energization time
NA s
Max. permitted off-delay time
NA s

Measurements

Width
108 mm
Width
4.25196 inch
Height
90 mm
Height
3.54330 inch
Depth
67 mm
Depth
2.63779 inch

Logistics

Net weight
0.312 kg
Country of origin
Germany
Customs tariff number
85364900

Packaging

PackQuantityGTINGross weightDimensions (L × W × D)
BE0———