Photo 1 of 4
CM-PAS.31S Three-phase monitoring relay
- Manufacturer part no.
- EAN
- Series
- CM-PAS
Ordering
- Order unit
- piece
Description
The CM-PAS.31S relay is from the CM three-phase monitors range. This relay operates with a rated control supply voltage / three-phase measuring voltage of 160-300 V AC and has a 2 c/o output with contacts rated at 250 V / 4 A. The CM-PAS.31S monitors the phase parameters phase failure, phase sequence and phase unbalance. An ON-delay is adjustable over a range of instantaneous to 30 s (0, 0.1-30 s). A sealable transparent cover for protection against unauthorized changes is available as accessory. The device offers screw connection technology with double-chamber cage connection terminals.
Tender text
Mit den Dreiphasenüberwachungsrelais CM Reihe kann eine zuverlässige und kontinuierliche Überwachung eines Dreiphasennetzes, den störungsfreien und wirtschaftlichen Betrieb von Maschinen und Anlagen garantiert werden. Darum überwachen die Dreiphasenüberwachungsrelais der CM Reihe je nach Bedarf die Phasenspannungen, die Phasenfolge, die Phasenasymmetrie, das Vorhandensein aller Phasen sowie den Neutralleiter. Beschriftungsschilder, plombierbare Klarsichtabdeckungen und Adapter für Schraubmontage sind als Zubehör erhältlich. Normen: CAN/CSA C22.2 No.14, IEC/EN 63000, IEC/EN 60255-27, IEC/EN 61000-6-2, IEC/EN 61000-6-3, UL 508 Anschlussart: Schraubklemme Ausgang: 2 Wechsler Bemessungsbetriebsstrom AC-12: 4 A Bemessungsbetriebsstrom AC-15: 3 A Bemessungsbetriebsstrom DC-12: 4 A Bemessungsbetriebsstrom DC-13: 2 A Bemessungsisolationsspannung: 600 V, 300 V Bemessungssteuerspeisespannung: (L-L) 160 ... 300 V AC Funktion: Phasenfehlererkennung, Phasenfolgeüberwachung, Phasenschwankungserkennung Messbereich: (L-L) 160 ... 300 V AC Zeitbereich: 0 Sekunde(n)
Technical data
ETIM class: Phase monitoring relay (EC001441)
Connection
- Type of electric connection
- Screw connection
- Number of contacts as normally closed contact
- 2
- Number of contacts as normally open contact
- 2
- Number of contacts as change-over contact
- 2
Model/type
- With detachable clamps
- No
Electrical
- External power supply required
- No
- Voltage type (supply voltage)
- AC
- Supply voltage AC 50 Hz
- NA, - V
- Supply voltage AC 60 Hz
- NA, - V
- Supply voltage DC
- NA, - V
- Voltage measuring range
- -, - V
- Voltage type (operating voltage)
- AC
- Operating voltage AC 50 Hz
- -, - V
- Operating voltage AC 60 Hz
- -, - V
- Operating voltage DC
- NA, - V
- Rated switch current
- 4 A
Options
- Phase sequence monitoring
- Yes
- Phase failure detection
- Yes
- Function under voltage detection
- No
- Function overvoltage detection
- No
- Phase imbalance monitoring
- Yes
Setting/control
- Min. adjustable delay-on energization time
- NA s
- Min. adjustable off-delay time
- NA s
Operating conditions
- Max. permitted delay-on energization time
- NA s
- Max. permitted off-delay time
- NA s
Measurements
- Width
- 22.5 mm
- Width
- 0.885825 inch
- Height
- 85.6 mm
- Height
- 3.370072 inch
- Depth
- 103.7 mm
- Depth
- 4.082669 inch
Logistics
- Net weight
- 0.133 kg
- Country of origin
- Germany
- Customs tariff number
- 85364900
Packaging
| Pack | Quantity | GTIN | Gross weight | Dimensions (L × W × D) |
|---|---|---|---|---|