Skip to content
Eltracore

Photo 1 of 3

ABB

CM-IWN.1P Insulation monitoring relay

Manufacturer part no.
EAN
Series
CM-IWN
Guest price€626.94 / pcexcl. VATMinimum order 1Delivery in about 10 business days
Checking availability…
Sign in to see your personal price

Ordering

Order unit
piece

Description

The CM-IWN.1P serves to monitor insulation resistance in accordance with IEC 61557-8 in unearthed IT AC systems, IT AC systems with galvanically connected DC circuits, or unearthed IT DC systems with a voltage up to 400 V AC and 600 V DC. The measuring range can be extended up to 690 V AC and 1000 V DC by using the coupling unit CM-IVN. It can be configured to the requirements of the applications and therefore used multi-functional.

Tender text

Die hohe Zuverlässigkeit von IT-Systemen wird durch kontinuierliche Isolationsüberwachung gewährleistet. Eine Isolationsüberwachung erkennt sich entwickelnde Isolationsfehler und meldet, dass der Wert unter das Minimum gefallen ist. Dies verhindert eine Betriebsunterbrechung durch einen zweiten, schwereren Isolationsfehler. Die Isolationswächter dienen zur Überwachung des Isolationswiderstandes nach IEC 61557-8 in ungeerdeten IT-AC-Systemen, IT-AC-Systemen mit galvanisch verbundenen DC-Kreisen oder ungeerdeten IT-DC-Systemen. Die Geräte sind in der Lage, Regelkreise (1-phasig) oder Hauptstromkreise (3-phasig) zu überwachen. Isolationsüberwachungs-Gerätereihe für AC, DC oder AC/DC IT-Systeme bis 690 V AC oder 1000 V DC. Beschriftungsschilder, plombierbare Klarsichtabdeckungen und Adapter für Schraubmontage sind als Zubehör erhältlich. Normen: CAN/CSA C22.2 No.14, IEC/EN 63000, IEC/EN 61326-2-4, IEC/EN 61557-1, IEC/EN 61557-8, UL 508 Anschlussart: Steckklemme Ausgang: 2 x 1 oder 1 x 2 Wechsler, konfigurierbar Bemessungssteuerspeisespannung: 24 ... 240 V AC/DC Breite (Netto-Abmessung): 45 mm Funktion: Ungeschüzte AC-Systeme, Ungeschützte AC-Systeme, Ungeschützte gemischte AC / DC-Systeme, bis zu 400 V AC, bis zu 600 V DC Höhe (Netto-Abmessung): 85.6 mm Messbereich: 1 ... 200 kΩ Nettogewicht: 0.217 kg Netzableitkapazität: 20 µF Tiefe (Netto-Abmessung): 104.8 mm

Technical data

ETIM class: Insulation and earth fault monitoring relay (EC001444)

Connection

Type of electric connection
Other
Number of contacts as normally closed contact
2
Number of contacts as normally open contact
2
Number of contacts as change-over contact
2

Model/type

With detachable clamps
No
Function
For mixed system

Electrical

External power supply required
Yes
Voltage type (supply voltage)
AC/DC
Supply voltage AC 50 Hz
24, 240 V
Supply voltage AC 60 Hz
24, 240 V
Supply voltage DC
24, 240 V
Voltage measuring range
0, 600 V
Line capacity
20 µF
Response value impedance 1
1, 200 kOhm
Response value impedance 2
1, 200 kOhm
Voltage type (operating voltage)
AC
Operating voltage AC 50 Hz
230, 230 V
Operating voltage AC 60 Hz
230, 230 V
Operating voltage DC
NA, - V
Rated switch current
3 A

Other

Rated operating frequency
15, 400 Hz

Options

Indication of insulation value
No
Error registration possible
Yes

Measurements

Width
45 mm
Width
1.7716545 inch
Height
3.37008056 mm
Height
3.37008056 inch
Depth
104.8 mm
Depth
4.12598648 inch

Logistics

Net weight
0.217 kg
Country of origin
Germany
Customs tariff number
85364900

Packaging

PackQuantityGTINGross weightDimensions (L × W × D)
BE0———