The DS800 series residual circuit breaker with overcurrent protection (RCBO) is available as 2P, 3P and 4P device. It is for protection of end user against overload and short-circuit currents. The DS800 range offers several types of protection. Type A (pulse current sensitive residucal current protection device), type AC (alternating current sensitive residucal current protection devcie), type AS (pulse current sensitive residual current protection device - selective) and tpye A-AP-R (pulse current sensitive residual current protection devcie - short-time delay).
Tender text
FI/LS-Kombinationen (RCBOs) bieten Sachschutz sowie einen Schutz vor elektrisch gezündeten Bränden. Einsatzgebiete sind Industrieanwendungen. Normen: IEC 60947-2 Anzahl Pole: 4P Anzahl geschützter Pole: 4 Auslösecharakteristik: B Bemessungsfehlerstrom: 300 mA Bemessungsfrequenz: 50 … 60 Hz Bemessungsstrom: 125 A Zeitverzögerung FI: unverzögert Zubehör anbaubar: Ja
Technical data
ETIM class: Distributor assembly with combination RCCB/MCB (EC002281)
Electrical
- Rated current
- 125 A
- Rated fault current
- 300 mA
- Release characteristic
- B
- Breaking capacity
- 50 kA
Model/type
- Number of protected poles
- 4
- Number of earth leakage circuit breakers
- 1
Options
- Concurrently switching neutral conductor
- Yes
- Wiring on terminal block
- NA
Measurements
- Height
- 108.2 mm
- Height
- 4.259834 inch
- Width
- 227.5 mm
- Width
- 8.956675 inch
- Depth
- 82.3 mm
- Depth
- 3.240151 inch
Logistics
- Net weight
- 1,757 kg
- Country of origin
- Switzerland