Photo 1 of 4
S401M-K3NP MCB 2 Pole 3A
- Manufacturer part no.
- EAN
- Series
- S400NP
Ordering
- Order unit
- piece
Description
SMISSLINE TP S400M are a current limiting miniature circuit breakers. They have two different tripping mechanisms, the delayed thermal tripping mechanism for overload protection and the electromechanic tripping mechanism for short circuit protection. They are available in different characteristics (B,C,D,K), configurations (1P,1P+N,2P,3P,3P+N), breaking capacities (up to 10 kA at 240/415 V AC ) and rated currents (up to 63A). MCBs of the product range S400M are comply with IEC/EN 60898-1 for B,C and D characteristic and IEC/EN 60947-2 for C and K characteristic. The pluggable solution is only for the SMISSLINE TP System, allowing the use for commercial, industrial, and critical power applications.
Tender text
Sicherungsautomat zum Schutz vor Überlast und Kurzschluss von Kabel und Leitungen gemäß DIN VDE 0100-430 und DIN VDE 0100-530. Erfüllt die Bauvorschriften DIN VDE 0641-11 bzw. IEC/EN 60898-1, DIN VDE 0660-101 bzw. IEC/EN60947-2. Die Anschlussklemme sorgt für eine einfache und sichere Handhabung mittels einer Druckplatte. Leitungsquerschnitte bis zu 35 mm² können direkt an das Gerät über die Anschlussklemme mit Isolierung in Schutzklasse IP20 angeschlossen werden. Die Kontaktierung erfolgt direkt über das Stecksockelsystem Smissline TP. Die Aussenleiterkontaktierung kann frei gewählt werden (L1, L2 oder L3). Normen: IEC/EN 60947-2 Anschlussart: Schraubklemme Anzahl Pole: 2P Anzahl geschützter Pole: 2 Auslösecharakteristik: K Bemessungs-Grenzkurzschlussausschaltvermögen: 25 kA, 25 kA Bemessungsbetriebsspannung: 240 V Bemessungsschaltvermögen: 10 kA, 10 kA Bemessungsstrom: 3 A Zubehör anbaubar: Ja Schaltstellungsanzeige: Rot AN / Grün AUS
Technical data
ETIM class: Miniature circuit breaker (MCB) (EC000042)
Measurements
- Built-in depth
- 82 mm
- Built-in depth
- 3.22834 inch
- Width in number of modular spacings
- 2
Electrical
- Release characteristic
- K
- Rated current
- 3 A
- Rated voltage
- V
- Rated insulation voltage Ui
- 440 V
- Rated impulse withstand voltage Uimp
- 4 kV
- Rated short-circuit breaking capacity Icn according to EN 60898 at 230 V
- 10 kA
- Voltage type
- AC
- Rated short-circuit breaking capacity Icn according to EN 60898 at 400 V
- - kA
- Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 230 V
- 25 kA
- Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 400 V
- 25 kA
- Power loss
- 2.4 W
- Current limiting class
- 3
- Overvoltage category
- 3
Model/type
- Number of poles (total)
- 2
- Number of protected poles
- 2
Other
- Frequency
- 50, 60 Hz
- Pollution degree
- 3
Mounting/installation
- Flush-mounted installation
- No
Options
- Concurrently switching neutral conductor
- Yes
- Additional equipment possible
- Yes
Protection
- Degree of protection (IP)
- IP20
- Explosion-proof
- No
Operating conditions
- Ambient temperature during operating
- -25, 60 °C
- Ambient temperature during operating
- -13, 140 °F
Connection
- Connectable conductor cross section multi-wired
- 0.75, 25 mm²
- Connectable conductor cross section multi-wired
- 0.0011, 0.0387 in²
- Connectable conductor cross section solid-core
- 0.75, 35 mm²
- Connectable conductor cross section solid-core
- 0.0011, 0.0542 in²
Logistics
- Net weight
- 221 kg
- Country of origin
- Switzerland
- Customs tariff number
- 85362000
Packaging
| Pack | Quantity | GTIN | Gross weight | Dimensions (L × W × D) |
|---|---|---|---|---|
| BE | 0 | — | — | — |