Skip to content
Eltracore

Photo 1 of 3

ABB

AFDD+FI/LS, 10 kA, 3TE Fehlerlichtbogen-Schutzeinrichtung+FI/LS

Manufacturer part no.
EAN
Series
DS-ARC1 M
Guest price€189.07 / pcexcl. VATMinimum order 1Delivery in about 59 business daysSign in to see your personal price

Ordering

Order unit
piece

Description

DS-ARC1 M is a 1P+N arc fault detection device (AFDD) with an integrated RCBO in three modules, for the protection against earth arc faults, parallel arc faults, series arc faults, overvolatge, short-circuit currents, overload, earth fault currents

Tender text

Fehlerlichtbogen-Schutzeinrichtung (AFDD) mit FI/LS-Schalter (RCBO) nach IEC/EN 62606 (VDE 0665-10) und IEC/EN 61009-1 (VDE 0664-20), IEC/EN 61009-2-1 (VDE 0664-21) bieten Schutz vor seriellen und parallelen Fehlerlichtbögen, Schutz vor Überstrom (Überlast oder Kurzschluss), Schutz bei sinusförmigen Wechselströmen und pulsierenden Strömen mit glattem Gleichfehlerstrom von bis zu 6 mA gegen Erde, Schutz vor Überspannung (nur für AFDD intern) und Schutz vor elektrisch gezündeten Bränden gemäß DIN VDE 0100-420. Einspeisung von oben oder unten beliebig, Querverdrahtung im hinteren Klemmenbereich möglich. Isolationsprüfung (DS-ARC1 ausschalten): bis 1000 V AC/DC Abklemmen der Leitungen nicht nötig, > 1000 V AC/DC Leitungen müssen abgeklemmt werden. LED-Funktionsüberwachung, kontinuierlicher interner Selbsttest. LED-Fehlerspeicher zum Abruf, Löschen des letzten Auslösegrundes. Zubehör des System pro M compact® anbaubar, unten anbaubarer Hilfsschalter. AFDD+RCBO DS-ARC1M ist 1polig geschützt (LS), 2polig schaltend. Normen: IEC/EN 62606, IEC/EN 61009-1, IEC/EN 61009-2-1 Anzahl Pole: 1P+N Anzahl geschützter Pole: 1 Auslösecharakteristik: C Bemessungsbetriebsspannung: 230...240 V AC Bemessungsfehlerstrom: 30 mA Bemessungsfrequenz: 50 … 60 Hz Bemessungsschaltvermögen: 10 kA Bemessungsstrom: 20 A Zeitverzögerung FI: unverzögert Breite in Teilungseinheiten: 3 Fehlerstromart: Typ A Schutzart: IP20, IP40 Zubehör anbaubar: Ja

Technical data

ETIM class: Earth leakage circuit breaker with auxiliary device (EC002695)

Electrical

Number of poles
2
Rated voltage
240 V
Rated insulation voltage Ui
- V
Rated impulse withstand voltage Uimp
- kV
Rated current
20 A
Rated fault current
0.03 A
Frequency
50
Leakage current type
-
Current limiting class
3
Power loss
- W
Rated short-circuit breaking capacity according to EN 61009
10 kA
Rated short-circuit breaking capacity according to IEC 60947-2
10 kA
Rated short-circuit breaking capacity Icn according to EN 61009-1
- kA
Surge current capacity
- kA
Voltage type
-
Release characteristic
C
Overvoltage category
3
Rated switch current auxiliary device
- A
Rated voltage auxiliary device
- V
Control voltage type auxiliary equipment
-

Model/type

Number of poles (total)
2
Number of protected poles
1
With interlocking device
-
Additional equipment attached at delivery
-

Mounting/installation

Mounting method
-

Connection

Disconnection characteristic
-
Connectable conductor cross section solid-core
-, - mm²
Connectable conductor cross section solid-core
-, - in²
Connectable conductor cross section multi-wired
1, 25 mm²
Connectable conductor cross section multi-wired
-, - in²

Other

Frequency
-
Pollution degree
2

Options

Concurrently switching neutral conductor
Yes
Anti-nuisance tripping version
-

Operating conditions

Ambient temperature during operating
-40, 70 °C
Ambient temperature during operating
-, - °F

Measurements

Width in number of modular spacings
3
Built-in depth
69 mm
Built-in depth
2.71653 inch

Protection

Degree of protection (IP)
-

Logistics

Net weight
240 kg
Country of origin
Italy
Customs tariff number
85363030

Packaging

PackQuantityGTINGross weightDimensions (L × W × D)