Photo 1 of 4
FI-Schalter Typ A 110V RCCB, 2P, 63A, 30mA, f.110V AC-Netz
- Manufacturer part no.
- EAN
- Series
- F200
Ordering
- Order unit
- piece
Description
The RCCBs F200 series assures protection against the effects of sinusoidal alternating and direct pulsating earth fault currents, protection, against indirects contacts and additional protection against direct contacts. Applications: residential, commercial, industrial. This particular serias has the minimum operating voltage of test buttom 0f 110V and it is suitable for application at 230V.
Tender text
Fehlerstrom-Schutzschalter (RCCBs) bieten Personen- und Sachschutz sowie einen Schutz vor elektrisch gezündeten Bränden gemäß DIN VDE 0100-410 und DIN VDE 0100-530. Die Fehlerstrom-Schutzschalter der Baureihe F200 Typ A gewährleisten Schutz bei sinusförmigen Wechselströmen und pulsierenden Strömen gegen Erde. Die F200 A 110 V Baureihe hat keine VDE Zulassung und ist speziell für 110 V AC bis 230/400 V AC Anwendungen einsetzbar. Sie erfüllen die Produktnormen IEC 61008-1, IEC 61008-2-1. Die Zulassungen sind: CCC und UL 1053.Anschlussöffnung für Leitungen liegt oberhalb von der Anschlussöffnung für die Phasenschiene für F200 A bis 63 A. Zubehör wie Hilfs- und Signalschalter sind am Gerät ohne Zusatzverdrahtung anbaubar. Normen: IEC 61008, UL 1053 Anzahl Pole: 2P Bemessungsfehlerstrom: 30 mA Bemessungsfrequenz: 50 … 60 Hz Bemessungsspannung: 230 V Bemessungsstrom: 63 A Zeitverzögerung FI: unverzögert Breite in Teilungseinheiten: 2 Fehlerstromart: Typ A Schutzart: IP20, IP40 Zubehör anbaubar: Ja
Technical data
ETIM class: Residual current circuit breaker (RCCB) (EC000003)
Electrical
- Number of poles
- 2
- Rated voltage
- - V
- Rated current
- 63 A
- Rated fault current
- NA A
- Rated insulation voltage Ui
- - V
- Rated impulse withstand voltage Uimp
- 4 kV
- Power loss
- - W
- Leakage current type
- A
- Short-circuit breaking capacity (Icw)
- NA kA
- Surge current capacity
- NA kA
- Voltage type
- -
Mounting/installation
- Mounting method
- DIN rail
Protection
- Selective protection
- No
- Degree of protection (IP)
- IP20
- Explosion-proof
- No
Model/type
- Short-time delayed tripping
- No
- With interlocking device
- Yes
- Type of personal protection PRCD
- -
Other
- Frequency
- Other
- Pollution degree
- 2
Options
- Additional equipment possible
- Yes
Measurements
- Width in number of modular spacings
- 2
- Built-in depth
- 69 mm
- Built-in depth
- 2.71653 inch
- Device width
- 35 mm
- Device width
- 1.37795 inch
- Device height
- 85 mm
- Device height
- 3.34645 inch
- Device depth
- 69 mm
- Device depth
- 2.71653 inch
Operating conditions
- Ambient temperature during operating
- -25, 55 °C
- Ambient temperature during operating
- -13, 131 °F
Connection
- Connectable conductor cross section multi-wired
- 0, 25 mm²
- Connectable conductor cross section multi-wired
- 0, 0.0387 in²
- Connectable conductor cross section solid-core
- 25, 25 mm²
- Connectable conductor cross section solid-core
- 0.0387, 0.0387 in²
Colour
- Colour
- -
- RAL-number (similar)
- 7035
Logistics
- Net weight
- 200 kg
- Country of origin
- Italy
- Customs tariff number
- 85363030
Packaging
| Pack | Quantity | GTIN | Gross weight | Dimensions (L × W × D) |
|---|---|---|---|---|
| BE | 0 | — | — | — |