Type B residual current circuit-breakers are AC-DC sensitive. The SK characteristic limits the risk of unwanted tripping providing maximum system availability, for frequencies ranging from 0 to 150 kHz. With low tripping sensitivity at higher frequencies, our SK circuit-breakers are perfectly suited for use in facilities where preventive fire protection measures are provided by additional means. Standard RCCBs are designed for circuits with 230 V at 50 Hz. The HD design makes our RCCBs particularly resistant to harmful environmental influences and therefore suitable for harsh environments.

Tender text

Allstromsensitiver Fehlerstromschutzschalter (RCCB) zur Erfassung von Wechsel-, pulsierenden und glatten Gleichfehlerströmen sensitiv für Fehlerströme und Mischfrequenzen von 0 Hz bis 150 kHz HD-Ausführung für den Einsatz in rauen Umgebungen doppelte Verdrahtungsebene oben und unten Schaltstellungsanzeige und Multifunktionsschaltknebel mit den Funktionen "ein", "aus" und "ausgelöst" (Mittelstellung) Sichtfenster für Beschriftungsetiketten Fehlerstromtyp: B Auslösekennlinientyp: SK Bemessungsfehlerstrom IΔn: 0.3 A kurzzeitverzögert (gewitterfest) Neutralleiterposition: beliebig Breite in Teilungseinheiten: 2 Polzahl (gesamt): 2 Bemessungsspannung (AC): 230 V Bemessungsstrom AC (typ.): 63 A Bemessungsfrequenz: 50 Hz Schraubklemme oben und unten (Laststromkreis): Anschlussquerschnitt eindrähtig: 1-Leiter: 1,5 mm² ... 50 mm²; 2-Leiter: 1,5 mm² ... 16 mm² Anschlussquerschnitt mehrdrähtig: 1-Leiter: 1,5 mm² ... 50 mm²; 2-Leiter: 1,5 mm² ... 16 mm² Anschlussquerschnitt feindrähtig: 1-Leiter: 1,5 mm² ... 50 mm²; 2-Leiter: 1,5 mm² ... 16 mm² Anschlussquerschnitt AWG, eindrähtig: 15 ... 1 Anschlussquerschnitt AWG, mehrdrähtig: 15 ... 1 Anschlussquerschnitt AWG, feindrähtig: 15 ... 1 Anschlussquerschnitt AWG, feindrähtig mit AEH: 15 ... 1 Umgebungstemperatur: min. -25 °C ... max. 60 °C Gehäuseart: Verteilereinbaugehäuse Montageart: Tragschiene (35 mm) Schutzart: IP20 (eingebaut: IP40) Abmessungen: B 36 mm (2 TE) × H 85 mm × T 75 mm Zertifizierungen: VDE Bauvorschriften/Normen: VDE 0664-10, VDE 0664-40, ÖVE/ÖNORM E 8601, DIN EN 61008-1, EN 62423 Fabrikat: Doepke oder gleichwertig Artikelbezeichnung: DFS 2 063-2/0,30-B SK HD Bestellnummer: 09146598HD gewähltes Fabrikat/Typ: ___________/___________

Technical data

ETIM class: Residual current circuit breaker (RCCB) (EC000003)

Electrical

Number of poles
2
Rated voltage
230 V
Rated current
63 A
Rated fault current
0.3 A
Rated insulation voltage Ui
400 V
Rated impulse withstand voltage Uimp
4 kV
Power loss
3.9 W
Leakage current type
B
Short-circuit breaking capacity (Icw)
10 kA
Surge current capacity
3 kA
Voltage type
AC

Mounting/installation

Mounting method
DIN rail

Protection

Selective protection
No
Degree of protection (IP)
IP20
Explosion-proof
No

Model/type

Short-time delayed tripping
Yes
With interlocking device
Yes
Type of personal protection PRCD
UN

Other

Frequency
50 Hz
Pollution degree
2

Options

Additional equipment possible
Yes

Measurements

Width in number of modular spacings
2
Built-in depth
69 mm
Device width
36 mm
Device height
85 mm
Device depth
75 mm

Operating conditions

Ambient temperature during operating
-25, 60 °C

Connection

Connectable conductor cross section multi-wired
1.5, 50 mm²
Connectable conductor cross section solid-core
1.5, 50 mm²

Colour

Colour
Grey
RAL-number (similar)
7035

Logistics

Net weight
0.261 kg
Country of origin
Germany
Customs tariff number
85363030

Packaging

PackQuantityGTINGross weightDimensions (L × W × D)
carton140147122467680.261 kg90 × 40 × 80 mm
carton40401471224677510.7 kg410 × 385 × 100 mm