Photo 1 of 4
RCCB 2p, 80A, 0.5A, Type A, Twin design, selective
- Manufacturer part no.
- EAN
Ordering
- Order unit
- piece
Description
Type A residual current circuit breakers are sensitive to pulsating and alternating currents. The twin version offers you the unique option of testing the switch without switching off the circuit. To do this, two complete RCCBs are combined in the device. When the test button is pressed, only one of the switches trips, while the other continues to carry the current and perform the protective function ensuring trouble-free operation. Selective circuit-breakers (S) are the ideal solution for systems with tiered distribution. In the event of a fault, only the downstream breaker in the affected section trips – ensuring targeted disconnection.
Tender text
Netzspannungsunabhängiger Fehlerstromschutzschalter (RCCB) zur Erfassung von Wechselfehler- und pulsierenden Gleichfehlerströmen redundante Ausführung zur Funktionsüberprüfung ohne Spannungsunterbrechung doppelte Verdrahtungsebene oben und unten Schaltstellungsanzeige und Multifunktionsschaltknebel mit den Funktionen "ein", "aus" und "ausgelöst" (Mittelstellung) Sichtfenster für Beschriftungsetiketten Fehlerstromtyp: A Bemessungsfehlerstrom IΔn: 0.5 A selektive Ausführung Neutralleiterposition: beliebig Breite in Teilungseinheiten: 4 Polzahl (gesamt): 2 Bemessungsspannung (AC): 230 V Bemessungsstrom AC (typ.): 80 A Bemessungsfrequenz: 50 Hz Schraubklemme oben und unten (Laststromkreis): Anschlussquerschnitt eindrähtig: 1-Leiter: 1,5 mm² ... 50 mm²; 2-Leiter: 1,5 mm² ... 16 mm² Anschlussquerschnitt mehrdrähtig: 1-Leiter: 1,5 mm² ... 50 mm²; 2-Leiter: 1,5 mm² ... 16 mm² Anschlussquerschnitt feindrähtig: 1-Leiter: 1,5 mm² ... 50 mm²; 2-Leiter: 1,5 mm² ... 16 mm² Anschlussquerschnitt AWG, eindrähtig: 15 ... 1 Anschlussquerschnitt AWG, mehrdrähtig: 15 ... 1 Anschlussquerschnitt AWG, feindrähtig: 15 ... 1 Anschlussquerschnitt AWG, feindrähtig mit AEH: 15 ... 1 Umgebungstemperatur: min. -25 °C ... max. 40 °C Gehäuseart: Verteilereinbaugehäuse Montageart: Tragschiene (35 mm) Schutzart: IP20 (eingebaut: IP40) Abmessungen: B 72 mm (4 TE) × H 97 mm × T 77 mm Bauvorschriften/Normen: VDE 0664-10, DIN EN 61008-1 Fabrikat: Doepke oder gleichwertig Artikelbezeichnung: DFS 2 080-2/0,50-A S Twin Bestellnummer: 09157015 gewähltes Fabrikat/Typ: ___________/___________
Technical data
ETIM class: Residual current circuit breaker (RCCB) with auxiliary device (EC002693)
Electrical
- Number of poles
- 2
- Rated voltage
- 230 V
- Rated current
- 80 A
- Rated fault current
- 0.5 A
- Rated insulation voltage Ui
- UN V
- Rated impulse withstand voltage Uimp
- 4 kV
- Power loss
- 4 W
- Leakage current type
- A
- Short-circuit breaking capacity (Icw)
- 10 kA
- Surge current capacity
- 5 kA
- Voltage type
- AC
- Rated switching capacity
- 0.8 kA
- Rated switch current auxiliary device
- 80 A
- Rated voltage auxiliary device
- 230 V
- Control voltage type auxiliary equipment
- UN
Mounting/installation
- Mounting method
- DIN rail
Protection
- Selective protection
- Yes
- Degree of protection (IP)
- IP20
- Explosion-proof
- No
Model/type
- Short-time delayed tripping
- No
- With interlocking device
- Yes
- Additional equipment integrated
- UN
- Additional equipment attached at delivery
- Protected redundancy circuit
Other
- Frequency
- 50 Hz
- Pollution degree
- 2
Measurements
- Width in number of modular spacings
- 4
- Built-in depth
- 69 mm
- Construction size according to DIN 43880
- 4
Colour
- Colour
- Grey
- RAL-number (similar)
- 7035
Operating conditions
- Ambient temperature during operating
- -25, 40 °C
Connection
- Connectable conductor cross section solid-core
- 1.5, 50 mm²
- Connectable conductor cross section multi-wired
- 1.5, 50 mm²
Logistics
- Net weight
- 0.59 kg
- Country of origin
- Germany
- Customs tariff number
- 85363030
Packaging
| Pack | Quantity | GTIN | Gross weight | Dimensions (L × W × D) |
|---|---|---|---|---|
| carton | 1 | 4014712208162 | 0.59 kg | 110 × 90 × 72 mm |