Skip to content
Eltracore

Photo 1 of 4

Doepke

Circuit-breaker with RCCB 4-pole, 0.03A, 160A@230/400V (AC), 50Hz, AC/DC sensitive, NK-Characteristic

Manufacturer part no.
EAN
Price on requestAsk us for a quote for this product.
Checking availability…

Ordering

Order unit
piece

Description

Circuit-breakers with residual current trip (CBR) switch high currents, protect equipment, cables and lines against overcurrent and protect people against electric shock. DFL 8 are compact devices with integrated auxiliary switch and terminals for large conductor cross-sections. Type B residual current circuit-breakers are AC-DC sensitive. Switches with the characteristic curve NK provide classic fire protection of 300 mA at frequencies up to 150 kHz. They are optimised for facilities at risk of fire. Switches of this variant have a fixed residual response current of 30 mA for the protection of persons. They therefore provide fault and fire protection as well as additional protection (personal protection, protection in the event of direct contact). Standard RCCBs are designed for circuits with 230/400 V at 50 Hz.

Tender text

Leistungsschalter mit Fehlerstromauslöser (CBR), 4polig, in Kompaktbauweise, mit kurzschlussstrombegrenzendem Kontaktsystem, mit einstellbaren thermomagnetischen Auslösern, mit Kipphebel und 3 Schaltstellungen (Aus, Ausgelöst und Ein), entsprechend IEC/EN 60947-2, DIN VDE 0660. Fehlerstromtyp: B Auslösekennlinientyp: NK Bemessungsfehlerstrom IΔn: 0.03 A kurzzeitverzögert (gewitterfest) Neutralleiterposition: links Bemessungsbetriebsspannung: 400 V AC Betriebsfrequenz: 50 Hz Bemessungsstoßspannungsfestigkeit: 4 kV Bemessungsdauerstrom: 160 A Betriebstemperatur: min. -25 °C ... max. 70 °C Mechanische Lebensdauer: 2000 Schaltspiele Elektrische Lebensdauer AC-1: 10000 Schaltspiele Überlastauslöser: 0.8 - 1 x Ir Unverzögerter Kurzschlussauslöser Ii: 6 - 10 x Iu Hilfsschalter integriert: 1 Schließer, 1 Öffner, 0 Wechsler Rahmenklemme oben und unten (Laststromkreis): Klemmbereich: min. 4 mm² ... max. 185 mm² Anschlussquerschnitt eindrähtig: 1-Leiter: 4 mm² ... 16 mm²; 2-Leiter: 4 mm² ... 16 mm² Anschlussquerschnitt mehrdrähtig: 1-Leiter: 25 mm² ... 185 mm²; 2-Leiter: 25 mm² ... 70 mm² Gehäuseart: Aufputzgehäuse Montageart: Wandmontage Schutzart: IP20 (eingebaut: IP40) Abmessungen: B 140 mm × H 291 mm × T 103 mm Bauvorschriften/Normen: DIN IEC 60755, EN 60947-2, EN 60947-2 Anhang B, VDE 0660-101 Fabrikat: Doepke oder gleichwertig Artikelbezeichnung: DFL 8 160-4/0,03-B NK Bestellnummer: 09184783 gewähltes Fabrikat/Typ: ___________/___________

Technical data

ETIM class: Earth leakage circuit breaker (EC000905)

Model/type

Number of poles (total)
4
Number of protected poles
3
With interlocking device
Yes

Electrical

Rated voltage
400 V
Rated insulation voltage Ui
1000 V
Rated impulse withstand voltage Uimp
4 kV
Rated current
160 A
Rated fault current
0.03 A
Leakage current type
B
Current limiting class
UN
Power loss
93.4 W
Rated short-circuit breaking capacity according to EN 61009
UN kA
Rated short-circuit breaking capacity according to IEC 60947-2
85 kA
Rated short-circuit breaking capacity Icn according to EN 61009-1
UN kA
Surge current capacity
5 kA
Voltage type
AC
Release characteristic
Other
Overvoltage category
3

Mounting/installation

Mounting method
Surface mounting

Connection

Disconnection characteristic
Short-time delayed
Connectable conductor cross section solid-core
4, 16 mm²
Connectable conductor cross section multi-wired
25, 185 mm²

Other

Frequency
50 Hz
Pollution degree
3

Options

Concurrently switching neutral conductor
Yes
Anti-nuisance tripping version
No

Operating conditions

Ambient temperature during operating
-25, 70 °C

Measurements

Width in number of modular spacings
0
Built-in depth
149 mm

Protection

Degree of protection (IP)
IP20

Logistics

Net weight
5.84 kg
Country of origin
Germany
Customs tariff number
85363090

Packaging

PackQuantityGTINGross weightDimensions (L × W × D)
carton140147121536605.84 kg310 × 150 × 180 mm

Documents