Skip to content
Eltracore

Photo 1 of 3

Doepke

MCB 1p+N, B-characteristic, 25A/230V AC, 6kA, compact

Manufacturer part no.
EAN
Price on requestAsk us for a quote for this product.
Checking availability…

Ordering

Order unit
piece

Description

Miniature circuit-breakers protect cables, conductors, and installation devices against overload and short circuit. Each of our circuit-breakers is equipped with a trip-free mechanism that ensures safe disconnection – even if the toggle is mechanically blocked. The compact circuit-breakers of the ELS series monitor one phase and the neutral conductor. They are suitable for rated short-circuit currents up to 6 kA. With tripping characteristic B, these circuit-breakers ensure reliable protection for your circuits without high inrush currents.

Tender text

Leitungsschutzschalter (MCB) in kompakter Bauform für den Export. Platz sparende Installation, Kontaktstellungsanzeige rot-grün, Klemmhilfe-Hintersteckschutz, umfangreiches Zubehörprogramm nachträglich anbaubar Auslösecharakteristik (MCB): B Laststromkreis (Lasttrennkontakt): Polzahl (gesamt): 2 Bemessungsspannung (AC): 230 V Bemessungsstrom AC (typ.): 25 A Bemessungsfrequenz: 50 Hz, 60 Hz Bemessungskurzschlussstrom: 6 kA Bemessungsschaltvermögen nach EN 60898 bei 230 V: 6 kA Schraubklemme oben und unten (Laststromkreis): Anschlussquerschnitt eindrähtig: 1-Leiter: 1 mm² ... 10 mm² Anschlussquerschnitt mehrdrähtig: 1-Leiter: 1 mm² ... 10 mm² Umgebungstemperatur: min. -25 °C ... max. 50 °C Gehäuseart: Verteilereinbaugehäuse Montageart: Tragschiene (35 mm) Schutzart: IP40 Abmessungen: B 17,8 mm (1 TE) × H 80 mm × T 72 mm Bauvorschriften/Normen: EN 60898-1 Fabrikat: Doepke oder gleichwertig Artikelbezeichnung: ELS 3 B25/1+N Bestellnummer: 09915026 gewähltes Fabrikat/Typ: ___________/___________

Technical data

ETIM class: Miniature circuit breaker (MCB) (EC000042)

Measurements

Built-in depth
66 mm
Width in number of modular spacings
1

Electrical

Release characteristic
B
Rated current
25 A
Rated voltage
230 V
Rated insulation voltage Ui
UN V
Rated impulse withstand voltage Uimp
UN kV
Rated short-circuit breaking capacity Icn according to EN 60898 at 230 V
6 kA
Voltage type
AC
Rated short-circuit breaking capacity Icn according to EN 60898 at 400 V
0 kA
Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 230 V
UN kA
Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 400 V
UN kA
Power loss
1.6 W
Current limiting class
3
Overvoltage category
3

Model/type

Number of poles (total)
2
Number of protected poles
1

Other

Frequency
50, 60 Hz
Pollution degree
2

Mounting/installation

Flush-mounted installation
No

Options

Concurrently switching neutral conductor
Yes
Additional equipment possible
No

Protection

Degree of protection (IP)
IP40
Explosion-proof
No

Operating conditions

Ambient temperature during operating
-25, 50 °C

Connection

Connectable conductor cross section multi-wired
1, 10 mm²
Connectable conductor cross section solid-core
1, 10 mm²

Logistics

Net weight
0.122 kg
Country of origin
Romania
Customs tariff number
85362010

Packaging

PackQuantityGTINGross weightDimensions (L × W × D)
carton140147121374170.122 kg80 × 20 × 70 mm

Documents