RCBOs combine residual current protection and overcurrent protection in a single device. This makes them ideal for use in distribution boards where space is limited. The rated breaking capacity of the two-pole DRCBO 2 series is 10 kA. Type A circuit-breakers detect pulsating direct current and alternating current. With tripping characteristic B, these circuit-breakers ensure reliable protection for your circuits without high inrush currents. Standard circuit-breakers are designed for circuits with 230 V or 400 V at 50 Hz.

Tender text

Netzspannungsunabhängiger Fehlerstromschutzschalter mit Überstromauslösung (RCBO) zur Erfassung von Wechselfehler- und pulsierenden Gleichfehlerströmen geeignet zum nachträglichen Anbau von Zusatzeinrichtungen Auslösecharakteristik (MCB): B Fehlerstromtyp: A Bemessungsfehlerstrom IΔn: 0.3 A Neutralleiterposition: beliebig Breite in Teilungseinheiten: 2 Polzahl (gesamt): 2 Bemessungsspannung (AC): 230 V Bemessungsstrom AC (typ.): 32 A Bemessungsfrequenz: 50 Hz max. Bemessungsschaltvermögen: 10 kA Bemessungskurzschlussstrom: 6 kA Bemessungsisolationsspannung: 250 V Schraubklemme oben, unten (Laststromkreis): Klemmbereich: min. 1 mm² ... max. 25 mm² Anschlussquerschnitt eindrähtig: 1-Leiter: 1 mm² ... 25 mm² Anschlussquerschnitt mehrdrähtig: 1-Leiter: 1 mm² ... 16 mm² Anschlussquerschnitt feindrähtig: 1-Leiter: 1 mm² ... 16 mm² Umgebungstemperatur: min. -25 °C ... max. 40 °C Gehäuseart: Verteilereinbaugehäuse Montageart: Tragschiene (35 mm) Schutzart: IP20 (eingebaut: IP40) Abmessungen: B 35 mm (2 TE) × H 80 mm × T 74 mm Bauvorschriften/Normen: EN 61009, EN 61009-2-1 Fabrikat: Doepke oder gleichwertig Artikelbezeichnung: DRCBO 2 B32/0,30/2-A Bestellnummer: 09934117 gewähltes Fabrikat/Typ: ___________/___________

Technical data

ETIM class: Earth leakage circuit breaker (EC000905)

Model/type

Number of poles (total)
2
Number of protected poles
2
With interlocking device
No

Electrical

Rated voltage
230 V
Rated insulation voltage Ui
250 V
Rated impulse withstand voltage Uimp
4 kV
Rated current
32 A
Rated fault current
0.3 A
Leakage current type
A
Current limiting class
3
Power loss
UN W
Rated short-circuit breaking capacity according to EN 61009
10 kA
Rated short-circuit breaking capacity according to IEC 60947-2
UN kA
Rated short-circuit breaking capacity Icn according to EN 61009-1
6 kA
Surge current capacity
3 kA
Voltage type
AC
Release characteristic
B
Overvoltage category
3

Mounting/installation

Mounting method
DIN rail

Connection

Disconnection characteristic
Undelayed
Connectable conductor cross section solid-core
1, 25 mm²
Connectable conductor cross section multi-wired
1, 16 mm²

Other

Frequency
50 Hz
Pollution degree
2

Options

Concurrently switching neutral conductor
No
Anti-nuisance tripping version
No

Operating conditions

Ambient temperature during operating
-25, 40 °C

Measurements

Width in number of modular spacings
2
Built-in depth
68 mm

Protection

Degree of protection (IP)
IP20

Logistics

Net weight
0.214 kg
Country of origin
Romania
Customs tariff number
85362010

Packaging

PackQuantityGTINGross weightDimensions (L × W × D)
carton140147122814620.214 kg87 × 42 × 80 mm
carton60401471228147913.24 kg390 × 185 × 235 mm