Photo 1 of 3
FI/LS circuit breaker combination (RCBO) 2p, 0.03A, 20A@230V (AC), C-characteristic, Type A, acc. to NEK 400-8-823
- Manufacturer part no.
- EAN
Ordering
- Order unit
- piece
Description
RCBOs combine residual current protection and overcurrent protection in a single device. This makes them ideal for use in distribution boards where space is limited. The rated breaking capacity of the two-pole DRCBO 2 series is 10 kA. Type A circuit-breakers detect pulsating direct current and alternating current. With tripping characteristic C, these circuit-breakers ensure reliable protection for your circuits with loads that generate higher inrush peaks. RCBO type AK have been specially developed for the Norwegian market. According to the Norwegian electrical standard NEK 400-8-823, AK types meet all requirements for tripping characteristics of I<sub>2</sub> <= I<sub>Z</sub>.
Tender text
Netzspannungsunabhängiger Fehlerstromschutzschalter mit Überstromauslösung (RCBO) zur Erfassung von Wechselfehler- und pulsierenden Gleichfehlerströmen geeignet zum nachträglichen Anbau von Zusatzeinrichtungen Auslösecharakteristik (MCB): C Fehlerstromtyp: A Bemessungsfehlerstrom IΔn: 0.03 A Neutralleiterposition: beliebig Breite in Teilungseinheiten: 2 Polzahl (gesamt): 2 Bemessungsspannung (AC): 230 V Bemessungsstrom AC (typ.): 20 A Bemessungsfrequenz: 50 Hz max. Bemessungsschaltvermögen: 10 kA Bemessungskurzschlussstrom: 10 kA Bemessungsisolationsspannung: 250 V Schraubklemme oben, unten (Laststromkreis): Klemmbereich: min. 1 mm² ... max. 25 mm² Anschlussquerschnitt eindrähtig: 1-Leiter: 1 mm² ... 25 mm² Anschlussquerschnitt mehrdrähtig: 1-Leiter: 1 mm² ... 16 mm² Anschlussquerschnitt feindrähtig: 1-Leiter: 1 mm² ... 16 mm² Umgebungstemperatur: min. -25 °C ... max. 40 °C Gehäuseart: Verteilereinbaugehäuse Montageart: Tragschiene (35 mm) Schutzart: IP20 (eingebaut: IP40) Abmessungen: B 35 mm (2 TE) × H 80 mm × T 74 mm Bauvorschriften/Normen: EN 61009, EN 61009-2-1 Fabrikat: Doepke oder gleichwertig Artikelbezeichnung: DRCBO 2 C20/0,03/2-A AK Bestellnummer: 09934525 gewähltes Fabrikat/Typ: ___________/___________
Technical data
ETIM class: Earth leakage circuit breaker (EC000905)
Model/type
- Number of poles (total)
- 2
- Number of protected poles
- 2
- With interlocking device
- No
Electrical
- Rated voltage
- 230 V
- Rated insulation voltage Ui
- 250 V
- Rated impulse withstand voltage Uimp
- 4 kV
- Rated current
- 20 A
- Rated fault current
- 0.03 A
- Leakage current type
- A
- Current limiting class
- 3
- Power loss
- 6 W
- Rated short-circuit breaking capacity according to EN 61009
- 10 kA
- Rated short-circuit breaking capacity according to IEC 60947-2
- UN kA
- Rated short-circuit breaking capacity Icn according to EN 61009-1
- 10 kA
- Surge current capacity
- 3 kA
- Voltage type
- AC
- Release characteristic
- C
- Overvoltage category
- 3
Mounting/installation
- Mounting method
- DIN rail
Connection
- Disconnection characteristic
- Undelayed
- Connectable conductor cross section solid-core
- 1, 25 mm²
- Connectable conductor cross section multi-wired
- 1, 16 mm²
Other
- Frequency
- 50 Hz
- Pollution degree
- 2
Options
- Concurrently switching neutral conductor
- No
- Anti-nuisance tripping version
- No
Operating conditions
- Ambient temperature during operating
- -25, 40 °C
Measurements
- Width in number of modular spacings
- 2
- Built-in depth
- 68 mm
Protection
- Degree of protection (IP)
- IP20
Logistics
- Net weight
- 0.258 kg
- Country of origin
- Romania
- Customs tariff number
- 85362010
Packaging
| Pack | Quantity | GTIN | Gross weight | Dimensions (L × W × D) |
|---|---|---|---|---|
| carton | 1 | 4014712282308 | 0.258 kg | 87 × 42 × 80 mm |
| carton | 60 | 4014712282315 | 15.63 kg | 390 × 185 × 235 mm |