Skip to content
Eltracore

Photo 1 of 3

Doepke

Fire protection sw. 2p, 25A, 0.03A, C-characteristic, Type A, short-time delayed

Manufacturer part no.
EAN
Price on requestAsk us for a quote for this product.

Ordering

Order unit
piece

Description

Fire protection switches, arc-fault detection devices (AFDD) reduce the risk of fire caused by defects in the electrical installation. They disconnect the affected part of the system when serial and parallel arc faults occur. There are, as laid down in DIN VDE 0100-420, stipulated for common rooms and bedrooms in nurseries, nursing homes and accessible housing, as well as facilities at risk of fire. DAFDD 1 combine the detection of arc faults with line protection and protection against residual currents in a compact package. The contact position indicators and the display tripped by residual current provide a quick overview. The RCBO component of this switch offers protection against residual currents of Type A independent of the mains voltage as well as against short-circuit and overload. Switches with tripping characteristic C are optimised for electric circuits with high inrush or peak currents. Because of their response delay, KV switches are less sensitive to momentary pulse-type residual currents. As devices that are short-time delayed and at the same time lightning-resistant, they increase system availability and can as a general rule be used in place of standard switches because the short-time delay has no bearing on the additional protection (of people).

Tender text

Fehlerstromschutzschalter mit Überstromauslösung (RCBO) und Fehlerlichtbogenerkennung (Brandschutzschalter) Das Gerät ist für die Erfassung von Wechselfehler- und pulsierenden Gleichfehlerströmen sowie von Fehlerlichtbögen geeignet. Auslösecharakteristik (MCB): C Fehlerstromtyp: A Bemessungsfehlerstrom IΔn: 0.03 A kurzzeitverzögert (gewitterfest) Neutralleiterposition: links, rechts Breite in Teilungseinheiten: 3 Laststromkreis (Lasttrennkontakt): Polzahl (gesamt): 2 Bemessungsspannung (AC): 240 V Bemessungsstrom AC (typ.): 25 A Bemessungsfrequenz: 50 Hz max. Bemessungsschaltvermögen: 10 kA Bemessungskurzschlussstrom: 10 kA Bemessungsisolationsspannung: 250 V Schraubklemme oben, unten (Laststromkreis): max. Leitungslänge: 70 m Anschlussquerschnitt eindrähtig: 1-Leiter: 1 mm² ... 25 mm² Anschlussquerschnitt mehrdrähtig: 1-Leiter: 1 mm² ... 16 mm² Anschlussquerschnitt feindrähtig: 1-Leiter: 1 mm² ... 16 mm² Umgebungstemperatur: min. -25 °C ... max. 40 °C Gehäuseart: Verteilereinbaugehäuse Montageart: Tragschiene (35 mm) Schutzart: IP20 (eingebaut: IP40) Abmessungen: B 54 mm (3 TE) × H 80 mm × T 76 mm Zertifizierungen: VDE Bauvorschriften/Normen: EN 62606, EN 61009 Fabrikat: Doepke oder gleichwertig Artikelbezeichnung: DAFDD 1 C25/0,03/2-A KV Bestellnummer: 09962504 gewähltes Fabrikat/Typ: ___________/___________

Technical data

ETIM class: Earth leakage circuit breaker with auxiliary device (EC002695)

Model/type

Number of poles (total)
2
Number of protected poles
2
With interlocking device
No
Additional equipment attached at delivery
Fire protection switch

Electrical

Rated voltage
240 V
Rated insulation voltage Ui
250 V
Rated impulse withstand voltage Uimp
UN kV
Rated current
25 A
Rated fault current
0.03 A
Leakage current type
A
Current limiting class
3
Power loss
5.6 W
Rated short-circuit breaking capacity according to EN 61009
10 kA
Rated short-circuit breaking capacity according to IEC 60947-2
UN kA
Rated short-circuit breaking capacity Icn according to EN 61009-1
10 kA
Surge current capacity
0.25 kA
Voltage type
AC
Release characteristic
C
Overvoltage category
3
Rated switch current auxiliary device
25 A
Rated voltage auxiliary device
240 V
Control voltage type auxiliary equipment
AC

Mounting/installation

Mounting method
DIN rail

Connection

Disconnection characteristic
Short-time delayed
Connectable conductor cross section solid-core
1, 25 mm²
Connectable conductor cross section multi-wired
1, 16 mm²

Other

Frequency
50 Hz
Pollution degree
2

Options

Concurrently switching neutral conductor
No
Anti-nuisance tripping version
No

Operating conditions

Ambient temperature during operating
-25, 40 °C

Measurements

Width in number of modular spacings
3
Built-in depth
70 mm

Protection

Degree of protection (IP)
IP20

Logistics

Net weight
0.277 kg
Country of origin
Czechia
Customs tariff number
85363030

Packaging

PackQuantityGTINGross weightDimensions (L × W × D)
carton140147122362020.277 kg86 × 55 × 75 mm
carton40401471223621911.999 kg385 × 180 × 230 mm

Documents