Skip to content
Eltracore

Eaton

Lightning current surge arrester for 40-mm bus bar, TN-S/TT, 3P, 7.5 kA (10/350)µs, class I+II+III/type 1+2+3

Manufacturer part no.
EAN
Price on requestAsk us for a quote for this product.
Checking availability…

Ordering

Order unit
piece

Description

Zum Schutz von Verbraucheranlagen im Netzanschlussraum des Zählerschranks an einer 40-mm-Sammelschiene vor transienten Überspannungen durch direkte und indirekte Blitzeinschläge sowie Schalthandlungen. Erfüllt alle Anforderungen für die Installation von Überspannungsschutz nach DIN VDE 0100-534, Prüfklassen I, II, III nach IEC 61643-1, SPD-Typ T1+2+3, entspricht IEC 61643-11: 2011, EN 61643 -11:2012+A11:2018, Blitzschutzklasse III und IV nach IEC 62305, Fehlerstromfrei

Technical data

ETIM class: Combined arrester for power supply systems (EC001457)

Options

System configuration DC
No
System configuration IT
No
System configuration TN
Yes
System configuration TN-C
No
System configuration TN-C-S
Yes
System configuration TN-S
Yes
System configuration TT
Yes
System configuration other
No
Remote signalling
No

Electrical

Number of poles
4
Lightning impulse current (10/350 µs)
7.5 kA
Max. continuous voltage AC
300 V
Max. continuous voltage DC
UN V
Nominal voltage AC
240 V
Nominal voltage DC
UN V
Max. PV-voltage
UN V
Voltage protection level
1.5 kV
Voltage protection level L-N
1.5 kV
Voltage protection level L-PE
UN kV
Voltage protection level N-PE
1.5 kV
Voltage protection level (DC+ - DC-)
UN kV
Voltage protection level (DC+/DC- - PE)
UN kV
Follow current extinguishing capability
0.1 kA
Max. overcurrent protection device, parallel connection (fuse)
160 A
Max. overcurrent protection device, series connection (fuse)
160 A
Voltage switching spark gap technology
Yes
Overcurrent protected voltage tapping
No

Other

Specific energy (W/R)
14 kJ/Ohm
Signalling at the device
Optical
Test class
Type 1 and 2 and 3

Mounting/installation

Mounting method
Busbar

Measurements

Construction size
2 modular spacing

Connection

Max. conductor cross section solid (solid, stranded)
UN mm²
Max. conductor cross section flexible (fine-strand)
UN mm²

Model/type

Integrated backup fuse
No

Protection

Energy-coordinated protection effect with regard to the terminal equipment
Yes
Degree of protection (IP)
IP20

Logistics

Net weight
0.633 kg
Country of origin
Slovenia
Customs tariff number
85363090

Packaging

PackQuantityGTINGross weightDimensions (L × W × D)
CS1—0.683 kg262 × 115 × 45 mm
carton24—16.692 kg370 × 360 × 240 mm
PF720—525.76 kg1,200 × 800 × 1,350 mm