Skip to content
Eltracore

ELKO EP

HRN-35

Manufacturer part no.
EAN
Price on requestAsk us for a quote for this product.

Ordering

Order unit
piece

Description

Serves to control supply voltage for appliances sensitive to supply tolerance, protection of the device against under/over voltage DESCRIPTION Controlling of supply voltage for appliances sensitive to supply tolerance. Same desing like HRN-33, but independent output relays for each voltage level. For example, the overload output can be switched to a different load than the under voltage. Supply from monitored voltage (monitors level of its own supply). Adjustable time delay for all types is 0 - 10 s (to eliminate short voltage drops or peaks). Voltage Umin adjusted as % of Umax. Starting a backup power supply when a power failure occurs. 1-phase desing. TECHNICAL PARAMETERS Power (monitored) voltage AC 48-276 V. Umax AC 160 – 276 V. Output contact: 1x changeover 16 A/AC1 (AgNi, 4 000 VA). 1-MODULE, DIN rail mounting.

Technical data

ETIM class: Voltage monitoring relay (EC001438)

Connection

Type of electric connection
Clip connection
Number of contacts as normally closed contact
1
Number of contacts as normally open contact
1
Number of contacts as change-over contact
1

Model/type

With detachable clamps
No

Electrical

Voltage measuring range 1
48, 276 V
Voltage measuring range 2
0, 0 V
Type of voltage measuring range
AC
Response value voltage
0, 0 V
Single-phase under voltage possible
Yes
Three-phase under voltage possible
No
Single-phase overvoltage possible
Yes
Rated control supply voltage AC 50 Hz
48, 276
Three-phase overvoltage possible
No
Rated control supply voltage AC 60 Hz
48, 276
Rated control supply voltage DC
0, 0
Voltage type for actuating
AC

Options

Single-phase hysteresis possible
No
Three-phase hysteresis possible
No
Contains function DC-under voltage
No
Contains function DC overvoltage
No
Contains function DC-voltage hysteresis
No

Setting/control

Min. adjustable delay-on energization time
0 s
Min. adjustable off-delay time
0 s

Operating conditions

Max. permitted delay-on energization time
10 s
Max. permitted off-delay time
10 s

Measurements

Width
17.6 mm
Height
90 mm
Depth
64 mm

Documents