HRN-43/230V
- Manufacturer part no.
- EAN
Ordering
- Order unit
- piece
Description
The full-featured monitoring relay is used for 3-phase network control, network monitoring and protection, voltage regulation from a generator or hydropower plant. DESCRIPTION Monitoring 3-phase mains: a) Voltage in 2 levels: overvoltage and undervoltage b) phase asymmetry c) phase sequence d) phase failure Function MEMORY – manual reset, “RESET” button on front pannel. Selectable function of 2nd relay (independent / parallel) Fixed T1(200ms) and adjustable T2 (0.1 – 10 s) delay to eliminate short voltage drops and peak. Monitoring relays in 2 variants: HRN-43: for circuits 3x400 V (without neutral) HRN-43N: for circuits 3x400/230 V (with neutral) TECHNICAL PARAMETERS Power voltage AC 230 V, AC 400 V, AC/DC 24 V, galvanically separated Umax: HRN-43: 240 – 480 V HRN-43N: 138 – 276 V Umin: 35 – 99% monitored voltage. Output contact: 2x changeover 16 A/250 V AC1 (AgNi, 2500 VA). 3-MODULE, DIN rail mounting.
Technical data
ETIM class: Voltage monitoring relay (EC001438)
Connection
- Type of electric connection
- Clip connection
- Number of contacts as normally closed contact
- 2
- Number of contacts as normally open contact
- 2
- Number of contacts as change-over contact
- 2
Model/type
- With detachable clamps
- No
Electrical
- Voltage measuring range 1
- 138, 276 V
- Voltage measuring range 2
- 0, 0 V
- Type of voltage measuring range
- AC
- Response value voltage
- 0, 0 V
- Single-phase under voltage possible
- Yes
- Three-phase under voltage possible
- Yes
- Single-phase overvoltage possible
- Yes
- Rated control supply voltage AC 50 Hz
- 230, 230
- Three-phase overvoltage possible
- Yes
- Rated control supply voltage AC 60 Hz
- 230, 230
- Rated control supply voltage DC
- 0, 0
- Voltage type for actuating
- AC
Options
- Single-phase hysteresis possible
- Yes
- Three-phase hysteresis possible
- Yes
- Contains function DC-under voltage
- No
- Contains function DC overvoltage
- No
- Contains function DC-voltage hysteresis
- No
Setting/control
- Min. adjustable delay-on energization time
- 0.1 s
- Min. adjustable off-delay time
- 0.1 s
Operating conditions
- Max. permitted delay-on energization time
- 10 s
- Max. permitted off-delay time
- 10 s
Measurements
- Width
- 52 mm
- Height
- 90 mm
- Depth
- 65 mm