Skip to content
Eltracore

ELKO EP

HRN-43 /400V

Manufacturer part no.
EAN
Price on requestAsk us for a quote for this product.

Ordering

Order unit
piece

Description

The full-featured monitoring relay is used for 3-phase network control, network monitoring and protection, voltage regulation from a generator or hydropower plant. DESCRIPTION Monitoring 3-phase mains: a) Voltage in 2 levels: overvoltage and undervoltage b) phase asymmetry c) phase sequence d) phase failure Function MEMORY – manual reset, “RESET” button on front pannel. Selectable function of 2nd relay (independent / parallel) Fixed T1(200ms) and adjustable T2 (0.1 – 10 s) delay to eliminate short voltage drops and peak. Monitoring relays in 2 variants: HRN-43: for circuits 3x400 V (without neutral) HRN-43N: for circuits 3x400/230 V (with neutral) TECHNICAL PARAMETERS Power voltage AC 230 V, AC 400 V, AC/DC 24 V, galvanically separated Umax: HRN-43: 240 – 480 V HRN-43N: 138 – 276 V Umin: 35 – 99% monitored voltage. Output contact: 2x changeover 16 A/250 V AC1 (AgNi, 2500 VA). 3-MODULE, DIN rail mounting.

Technical data

ETIM class: Voltage monitoring relay (EC001438)

Connection

Type of electric connection
Clip connection
Number of contacts as normally closed contact
2
Number of contacts as normally open contact
2
Number of contacts as change-over contact
2

Model/type

With detachable clamps
No

Electrical

Voltage measuring range 1
138, 276 V
Voltage measuring range 2
0, 0 V
Type of voltage measuring range
AC
Response value voltage
0, 0 V
Single-phase under voltage possible
Yes
Three-phase under voltage possible
Yes
Single-phase overvoltage possible
Yes
Rated control supply voltage AC 50 Hz
400, 400
Three-phase overvoltage possible
Yes
Rated control supply voltage AC 60 Hz
400, 400
Rated control supply voltage DC
0, 0
Voltage type for actuating
AC

Options

Single-phase hysteresis possible
Yes
Three-phase hysteresis possible
Yes
Contains function DC-under voltage
No
Contains function DC overvoltage
No
Contains function DC-voltage hysteresis
No

Setting/control

Min. adjustable delay-on energization time
0.1 s
Min. adjustable off-delay time
0.1 s

Operating conditions

Max. permitted delay-on energization time
10 s
Max. permitted off-delay time
10 s

Measurements

Width
52 mm
Height
90 mm
Depth
65 mm