Skip to content
Eltracore

ELKO EP

PRI-41/24V

Manufacturer part no.
EAN
Price on requestAsk us for a quote for this product.

Ordering

Order unit
piece

Description

To monitor overloading / discharge ( machine, motor...), load sensing, diagnostics of remote device (interrunption, short circuit, current cunsumption increase...) DESCRIPTION Monitoring adjusted current in 2 independent levels (overvoltage/undervoltage). MEMORY – function, “RESET” button on the frontal panel. Function of 2nd relay (independent/parallel): Adjustable time delay to eliminate short voltage drops and peak. Setting the Umax level (in% range) and the monitored Umin levels (in% of the set upper limit – function HYSTERESIS). Galvanically separated supply. TECHNICAL PARAMETERS Power voltage AC 230 V nebo AC/DC 24 V Monitored ranges: 1. range: 3.2 – 16 A (Input resistance 2.3 m?, max. permanent current 16 A) 2. range: 1 – 5 A (Input resistance 11 m?, max. permanent current 7.3 A) 3. range: 0.32 – 1.6 A (Input resistance 23 m?, max. permanent current 1.6 A) Output contact: 2x changeover 16 A/250 V AC1 (AgNi, 4 000 VA) for each current level. 3-MODULE, DIN rail mounting.

Technical data

ETIM class: Current monitoring relay (EC001440)

Connection

Type of electric connection
Clip connection
Number of contacts as normally closed contact
2
Number of contacts as normally open contact
2
Number of contacts as change-over contact
2

Model/type

With detachable clamps
No

Electrical

Current measuring range
0.32, 16 A
Rated control supply voltage AC 50 Hz
24, 24
Rated control supply voltage AC 60 Hz
24, 24
Single-phase under current possible
Yes
Rated control supply voltage DC
24, 24
Three-phase under current possible
No
Voltage type for actuating
AC/DC
Single-phase overcurrent possible
Yes
Three-phase overcurrent possible
No

Options

Single-phase hysteresis possible
Yes
Three-phase hysteresis possible
No
Contains function DC-voltage under current
Yes
Contains function DC-voltage overcurrent
Yes
Function DC-current hysteresis
Yes
External current transformer
UN

Setting/control

Min. adjustable delay-on energization time
0.1 s
Min. adjustable off-delay time
0.1 s

Operating conditions

Max. permitted delay-on energization time
10 s
Max. permitted off-delay time
10 s

Measurements

Width
52 mm
Height
90 mm
Depth
65 mm

Documents