Skip to content
Eltracore

Ensto

CC vertical angle crossarm 20 kV, H=550

Manufacturer part no.
EAN
Price on requestAsk us for a quote for this product.

Ordering

Order unit
piece

Description

For suspending double, three phase covered conductor lines in angles. Allowed loads for the crossarm at conductor fixing points are: Fx= 14.0 kN angle load Fz= 4.5 kN horizontally along conductor Fy= 4.0 kN vertically downwards. Dimensions A and B must be chosen so that the distances between live line parts and pole structure fulfil safety regulations. To meet the regulations, the minimum distances are A = 260 mm and B = 600 mm.

Technical data

ETIM class: Cross arm for utility pole (EC003515)

Model/type

Type
Angled cross arm
Profile shape
Other

Application

Suitable for
Two pole

Material

Material
Steel
Surface protection
Galvanised
Conductor surface
Covered

Electrical

Max. rated voltage
20 kV

Packaging

PackQuantityGTINGross weightDimensions (L × W × D)
carton0—25.9 kg0 × 0 × 0 mm
PX0—667.5 kg1,200 × 800 × 0 mm