For suspending double, three phase covered conductor lines in angles. Allowed loads for the crossarm at conductor fixing points are: Fx= 14.0 kN angle load Fz= 4.5 kN horizontally along conductor Fy= 4.0 kN vertically downwards. Dimensions A and B must be chosen so that the distances between live line parts and pole structure fulfil safety regulations. To meet the regulations, the minimum distances are A = 260 mm and B = 600 mm.
Technical data
ETIM class: Cross arm for utility pole (EC003515)
Model/type
- Type
- Angled cross arm
- Profile shape
- Other
Application
- Suitable for
- Two pole
Material
- Material
- Steel
- Surface protection
- Galvanised
- Conductor surface
- Covered
Electrical
- Max. rated voltage
- 20 kV
Packaging
| Pack | Quantity | GTIN | Gross weight | Dimensions (L × W × D) |
|---|---|---|---|---|
| carton | 0 | — | 25.9 kg | 0 × 0 × 0 mm |
| PX | 0 | — | 667.5 kg | 1,200 × 800 × 0 mm |