SURGE PROTECTION DEVICE

Manufacturer part no.
EAN
Guest price€43.24 / pcexcl. VATMinimum order 1Sign in to see your personal price

Ordering

Order unit
piece

Description

Surge protection device Mounting method: DIN rail (top hat rail) 35 mm With remote signalling contact: no Number of conductors (without earthing): 1 Construction size: 1 modular spacing Max. continuous voltage AC: 130 V. Nominal voltage AC: 110 V. Nominal voltage DC: 125 V. Category type 2: yes Voltage protection level L-N: 0.7 kV. Signalling at the device: Optic Max. continuous voltage DC: 170 V. Protection category: IP20 Voltage protection level N-PE: 0.7 kV. Integrated backup fuse: no System configuration DC: no System configuration IT: no System configuration TN: yes System configuration TN-C: yes System configuration TN-S: yes System configuration TT: no System configuration other: no System configuration TN-C-S: yes Max. discharge surge current (8/20): 40 kA. Short-circuit breaking capacity (Isccr): 50 kA.

Technical data

ETIM class: Surge protection device for power supply systems (EC000941)

Options

System configuration DC
No
System configuration IT
No
System configuration TN
Yes
System configuration TN-C
Yes
System configuration TN-C-S
Yes
System configuration TN-S
Yes
System configuration TT
No
System configuration other
No
Leakage-current free
UN

Electrical

Number of conductors (without earthing)
1
Nominal discharge surge current (8/20)
UN kA
Max. discharge surge current (8/20)
40 kA
Nominal voltage AC
110 V
Nominal voltage DC
125 V
Max. continuous voltage AC
130 V
Max. continuous voltage DC
170 V
Max. PV-voltage
UN V
Voltage protection level
UN kV
Voltage protection level L-N
0.7 kV
Voltage protection level N-PE
0.7 kV
Max. overcurrent protection device, parallel connection (fuse)
160 A
Max. overcurrent protection device, series connection (fuse)
UN A
Short-circuit breaking capacity (Isccr)
50 kA
Integrated short-circuit protection selective to fuse gG
UN A

Protection

Integrated short-circuit protection
UN
Degree of protection (IP)
IP20

Model/type

Integrated backup fuse
No
Category type 2
Yes

Mounting/installation

Mounting method
DIN rail (top hat rail) 35 mm

Measurements

Construction size
1 modular spacing

Connection

Max. conductor cross section solid (solid, stranded)
UN mm²
Max. conductor cross section flexible (fine-strand)
UN mm²

Communication

With remote signalling contact
No

Other

Signalling at the device
Optical

Logistics

Net weight
0.12 kg
Customs tariff number
85363030

Packaging

PackQuantityGTINGross weightDimensions (L × W × D)
piece180128234008220.14 kg83 × 125 × 27 mm