NH fuse-link gTr, 400VAC, size 3, 100KVA, top indicator/live tags
- Manufacturer part no.
- EAN
Ordering
- Order unit
- piece
Description
The NH system is classified among plug-in fuse systems and is composed of: fuse-base, (possibly including terminal covers and phase barriers) fuse-link with blade contact fuse-link replacement device (LV HRC fuse puller) Since the design of this system cannot guarantee non-interchangeability of rated current, it must be handled by a qualified professional. NH-fuse links „gTr“ are used for the protection of transformers. The time/current characteristic is especially adapted to that of the protected transformer and implies optimal selectivity to NH-fuse links characteristic gG. The fuses can be loaded with 1,3 times nominal current for up to 10 hours. The fuse link operates at 1,5 times nominal transformer current within 2 hours.
Tender text
Protection of transformers
Technical data
ETIM class: Knife blade fuse (EC000055)
Electrical
- Fuse construction type according to IEC 60269
- NH02
- Voltage type
- UN
- Rated current
- 144 A
- Rated switching capacity
- 100 kA
- Rated voltage AC
- 400 V
- Rated voltage DC
- UN V
- Power loss at rated current
- 9 W
Other
- Utilization category according to IEC 60269
- gTr
Model/type
- Type of fuse status indicator
- Other
Options
- Insulated metal gripping lugs (IMGL)
- No
Logistics
- Net weight
- 1 kg
- Dimensions (L × W × D)
- 150.1 × 50 × 88.9 mm
- Volume
- 1 l
- Country of origin
- Hungary
- Customs tariff number
- 85361090
Packaging
| Pack | Quantity | GTIN | Gross weight | Dimensions (L × W × D) |
|---|---|---|---|---|
| box | 1 | 33605340534468 | 1 kg | 160 × 89.9 × 74.9 mm |