Jistič
- Manufacturer part no.
- EAN
Price on requestAsk us for a quote for this product.
Ordering
- Order unit
- piece
Description
3pól, In 100 A, Icu 25 kA, charakteristika motorová M, nastavení IR 80 - 100 A, Cu/Al kabely 2,5 - 95 mm2
Technical data
ETIM class: Power circuit-breaker for trafo/generator/installation protection (EC000228)
Electrical
- Rated permanent current Iu
- 100 A
- Rated voltage
- 24, 690 V
- Rated short-circuit breaking capacity Icu at 400 V, 50 Hz
- 25 kA
- Overload release current setting
- 80, 100 A
- Adjustment range short-term delayed short-circuit release
- -, - A
- Adjustment range undelayed short-circuit release
- 1000, 1000 A
- Number of poles
- 3
Other
- Device construction
- Built-in device fixed built-in technique
Protection
- Integrated earth fault protection
- No
- Complete device with protection unit
- Yes
- Degree of protection (IP)
- IP40
Connection
- Type of electrical connection of main circuit
- Cable clamp
- Number of auxiliary contacts as normally closed contact
- -
- Number of auxiliary contacts as normally open contact
- -
- Number of auxiliary contacts as change-over contact
- -
- Position of connection for main current circuit
- Front side
Mounting/installation
- Suitable for DIN rail (top hat rail) mounting
- No
- DIN rail (top hat rail) mounting optional
- Yes
- EF007518
- false
Model/type
- With switched-off indicator
- Yes
- Type of control element
- Wing knob
- Motor drive integrated
- No
Options
- Motor drive optional
- Yes
Packaging
| Pack | Quantity | GTIN | Gross weight | Dimensions (L × W × D) |
|---|---|---|---|---|
| packet | 1 | 8590125202424 | 1.047 kg | 133 × 100 × 82 mm |