Schneider Electric Acti9 iC60N A9F74403 MCB, 4P, 3 A, curve C
- Manufacturer part no.
- EAN
- Series
- Acti9 iC60
Ordering
- Order unit
- piece
Description
The Schneider Electric Acti9 iC60N A9F74403 is a low-voltage miniature circuit breaker (MCB) that protects circuits against short circuits and overload currents. It has 4 poles (4P), all 4 protected, a rated current of 3 A and a C trip curve. Its ultimate short-circuit breaking capacity (Icu) is 50 kA from 220 V AC to 240 V AC according to EN/IEC 60947-2. Its rated short-circuit breaking capacity (Icn) is 6000 A at 400 V AC according to EN/IEC 60898-1. VisiTrip shows which circuit has tripped, reducing intervention time. The green VisiSafe strip confirms that the contacts are physically open before downstream maintenance. The fast-closing mechanism operates independently of manual actuation and helps extend service life. Electrical endurance is up to 10 000 cycles and mechanical endurance is up to 20 000 cycles. The rated insulation voltage (Ui) is 500 V AC. Current-limiting class 3 according to EN/IEC 60898-1 helps reduce the cost of downstream circuit protection. The breaker clips onto a DIN rail and is 8 increments of 9 mm wide. The pollution degree is 3 and the overvoltage category is IV. The breaker is white (RAL9003), measures 72 mm wide, 85 mm high and 78.5 mm deep, and has a stated net weight of 0.5 kg. According to IEC 60529, the degree of protection is IP20 for the device and IP40 in a class II modular enclosure. The operating temperature range is -35 °C to 70 °C, and the storage temperature range is -40 °C to 85 °C.
Technical data
ETIM class: Miniature circuit breaker (MCB) (EC000042)
Measurements
- Built-in depth
- 44.5 mm
- Width in number of modular spacings
- 4
Electrical
- Release characteristic
- C
- Rated current
- 3 A
- Rated voltage
- 400 V
- Rated insulation voltage Ui
- 500 V
- Rated impulse withstand voltage Uimp
- 6 kV
- Rated short-circuit breaking capacity Icn according to EN 60898 at 230 V
- NA kA
- Voltage type
- AC/DC
- Rated short-circuit breaking capacity Icn according to EN 60898 at 400 V
- 6 kA
- Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 230 V
- 50 kA
- Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 400 V
- 50 kA
- Power loss
- 2.2 W
- Current limiting class
- 3
- Overvoltage category
- 4
Model/type
- Number of poles (total)
- 4
- Number of protected poles
- 4
Other
- Frequency
- 50, 60 Hz
- Pollution degree
- 3
Mounting/installation
- Flush-mounted installation
- No
Options
- Concurrently switching neutral conductor
- No
- Additional equipment possible
- Yes
Protection
- Degree of protection (IP)
- IP20
- Explosion-proof
- No
Operating conditions
- Ambient temperature during operating
- -35, 70 °C
Connection
- Connectable conductor cross section multi-wired
- 1, 16 mm²
- Connectable conductor cross section solid-core
- 1, 25 mm²
Logistics
- Country of origin
- France
- Customs tariff number
- 8536201090