Acti9 iC60N A9F74601 Miniature Circuit Breaker, 1P+N, 1 A, C Curve
- Manufacturer part no.
- EAN
- Series
- Acti9 iC60
Ordering
- Order unit
- piece
Description
The Schneider Electric Acti9 iC60N A9F74601 is a low-voltage miniature circuit breaker (MCB) that protects AC circuits against short circuits and overloads. It has a 1P+N configuration with 1 protected pole, a rated current of 1 A and a C trip curve. Its ultimate short-circuit breaking capacity (Icu) is 50 kA at 220 to 240 V AC according to EN/IEC 60947-2. Its rated short-circuit breaking capacity (Icn) is 6000 A at 230 V AC according to EN/IEC 60898-1. The VisiTrip indicator identifies the affected circuit for faster intervention. The green VisiSafe strip indicates that the contacts are physically open for downstream maintenance. The quick-closing mechanism operates independently of manual action and helps extend service life. Electrical endurance is up to 10 000 cycles and mechanical endurance is up to 20 000 cycles. The rated insulation voltage Ui is 500 V AC. The breaker has current limiting class 3 according to EN/IEC 60898-1, pollution degree 3 and overvoltage category IV. The breaker clips onto a DIN rail and occupies 4 pitches of 9 mm. It is white (RAL9003), measures 36 mm in width, 85 mm in height and 78,5 mm in depth, and weighs 0,25 kg. According to IEC 60529, the degree of protection is IP20 for the breaker and IP40 in a modular enclosure. The operating temperature is -35 °C to 70 °C and the storage temperature is -40 °C to 85 °C.
Technical data
ETIM class: Miniature circuit breaker (MCB) (EC000042)
Measurements
- Built-in depth
- 44.5 mm
- Width in number of modular spacings
- 2
Electrical
- Release characteristic
- C
- Rated current
- 1 A
- Rated voltage
- 230 V
- Rated insulation voltage Ui
- 500 V
- Rated impulse withstand voltage Uimp
- 6 kV
- Rated short-circuit breaking capacity Icn according to EN 60898 at 230 V
- 6 kA
- Voltage type
- AC
- Rated short-circuit breaking capacity Icn according to EN 60898 at 400 V
- NA kA
- Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 230 V
- 50 kA
- Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 400 V
- NA kA
- Power loss
- 2.3 W
- Current limiting class
- 3
- Overvoltage category
- 4
Model/type
- Number of poles (total)
- 2
- Number of protected poles
- 1
Other
- Frequency
- 50, 60 Hz
- Pollution degree
- 3
Mounting/installation
- Flush-mounted installation
- No
Options
- Concurrently switching neutral conductor
- Yes
- Additional equipment possible
- Yes
Protection
- Degree of protection (IP)
- IP20
- Explosion-proof
- No
Operating conditions
- Ambient temperature during operating
- -35, 70 °C
Connection
- Connectable conductor cross section multi-wired
- 1, 16 mm²
- Connectable conductor cross section solid-core
- 1, 25 mm²
Logistics
- Country of origin
- France
- Customs tariff number
- 8536201090