Ersatzschutzmodul für Kombiableiter iPRD1 C25r 3P. geeignet für A9L1C325 (L-PE). Optische Funktions - / Defektanzeige des Ableiters (grün OK/ rot Gerät defekt). U0-Nennspannung 240 V AC (50/60Hz). Uc -höchste Dauerspannung 275V AC. In-Nennableitstossstrom 25 kA. Imax -maximaler Ableitstossstrom 65 kA. Iimp 25kA. Up-Schutzpegel 1,5 kV. Abmessung (B) 18mm x (H) 45mm x (T) 73.5mm. Gewicht 105g. Schutzart IP20 integriert. Betriebstemperatur -40 bis +85 Grad Celsius. Entspricht IEC 61643-11:2011, EN 61643-11:2012.

Technical data

ETIM class: Combined arrester for power supply systems (EC001457)

Options

System configuration DC
No
System configuration IT
No
System configuration TN
No
System configuration TN-C
Yes
System configuration TN-C-S
No
System configuration TN-S
No
System configuration TT
No
System configuration other
No
Remote signalling
UN

Electrical

Number of poles
1
Lightning impulse current (10/350 µs)
25 kA
Max. continuous voltage AC
275 V
Max. continuous voltage DC
UN V
Nominal voltage AC
240 V
Nominal voltage DC
UN V
Max. PV-voltage
UN V
Voltage protection level
1.5 kV
Voltage protection level L-N
UN kV
Voltage protection level L-PE
1.5 kV
Voltage protection level N-PE
UN kV
Voltage protection level (DC+ - DC-)
UN kV
Voltage protection level (DC+/DC- - PE)
UN kV
Follow current extinguishing capability
50 kA
Max. overcurrent protection device, parallel connection (fuse)
UN A
Max. overcurrent protection device, series connection (fuse)
UN A
Voltage switching spark gap technology
No
Overcurrent protected voltage tapping
UN

Other

Specific energy (W/R)
156.2 kJ/Ohm
Signalling at the device
Optical
Test class
Type 1 + 2

Mounting/installation

Mounting method
DIN rail (top hat rail) 35 mm

Measurements

Construction size
1 modular spacing

Connection

Max. conductor cross section solid (solid, stranded)
UN mm²
Max. conductor cross section flexible (fine-strand)
UN mm²

Model/type

Integrated backup fuse
No

Protection

Energy-coordinated protection effect with regard to the terminal equipment
Yes
Degree of protection (IP)
IP20

Logistics

Net weight
0.116 kg
Country of origin
Slovenia
Customs tariff number
85363030

Packaging

PackQuantityGTINGross weightDimensions (L × W × D)
piece136064868086030.116 kg28 × 54 × 96 mm
carton28136064868086003.563 kg400 × 300 × 150 mm
PF896—126.016 kg1,200 × 800 × 7,500 mm