Skip to content
Eltracore

Schneider Electric

Motor circuit breaker, TeSys Deca, 3P, 13-18 A, thermal magnetic, screw clamp terminals, TQ 24 units

Manufacturer part no.
EAN
Price on requestAsk us for a quote for this product.
Checking availability…

Ordering

Order unit
piece

Technical data

ETIM class: Motor protection circuit-breaker (EC000074)

Electrical

Overload release current setting
13, 18 A
Adjustment range undelayed short-circuit release
400, 400 A
Rated operating voltage
690, 690 V
Rated permanent current Iu
18 A
Rated operation power at AC-3, 230 V
4 kW
Rated operation power at AC-3, 400 V
7.5 kW
Power loss
2.5 W
With integrated under voltage release
No
Number of poles
3
Rated short-circuit breaking capacity Icu at 400 V, AC
15 kA

Model/type

With thermal overload protection
Yes
Type of control element
Rocker lever
With integrated auxiliary switch
No

Options

Phase failure sensitive
Yes

Other

Switch off technique
Thermomagnetic
Device construction
Complete device in housing

Connection

Type of electrical connection of main circuit
Screw connection

Protection

Degree of protection (IP)
IP20

Measurements

Height
89 mm
Width
45 mm
Depth
78.5 mm

Logistics

Customs tariff number
8536201090