Skip to content
Eltracore

Schneider Electric

Miniature circuit breaker (MCB), Multi9 C60SP, 4P, 2A, D curve, 10kA (UL1077), 10kA (IEC/EN 60947-2)

Manufacturer part no.
EAN
Series
Multi9
Price on requestAsk us for a quote for this product.

Ordering

Order unit
piece
Minimum order
3
Order in steps of
3

Description

Leitungsschutzschalter C60BP Multi 9 OEM, 10 kA. 1-polig, Nennstrom 45A, Z-Charakteristik, Betriebsspannung (Ue) 240V AC IEC/EN 60947-2 / 277V AC UL 489, Isolationsspannung (Ui) 500V AC. Einfach-Anschlussklemme für Kabel und Stiftkammschiene an der Geräteober- und unterseite. Befestigung über normalen Clipverschluss auf DIN-Schiene. Sprungschaltung für verschleißarmes Schalten der Kontakte. Zusätzlich anreihbare Hilfsmodule (optional)- Anzeige von Schaltstellung (OF), Fehlerauslösung (SD), Arbeitsstromauslöser (MX, MX+OF), Unterspannungsauslöser (MN, MNs, MNx). Werkzeuglose Montage linksseitig am Gerät. Der C60SP erfüllt folgende Normen- IEC/EN 60947-2, UL 489 / CSA C22.2 Nr.5 / GB 14048-2. Leitungsschutzschalter C60SP sind Multistandard-Leitungsschutzschalter die weltweit eingesetzt werden können, da sie alle internationalen und auch alle wichtigen nationalen Normen erfüllen.

Technical data

ETIM class: Miniature circuit breaker (MCB) (EC000042)

Measurements

Built-in depth
44 mm
Width in number of modular spacings
8

Electrical

Release characteristic
D
Rated current
2 A
Rated voltage
277 V
Rated insulation voltage Ui
500 V
Rated impulse withstand voltage Uimp
6 kV
Rated short-circuit breaking capacity Icn according to EN 60898 at 230 V
NA kA
Voltage type
AC
Rated short-circuit breaking capacity Icn according to EN 60898 at 400 V
NA kA
Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 230 V
20 kA
Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 400 V
10 kA
Power loss
1.7 W
Current limiting class
NA
Overvoltage category
4

Model/type

Number of poles (total)
4
Number of protected poles
4

Other

Frequency
50, 60 Hz
Pollution degree
3

Mounting/installation

Flush-mounted installation
No

Options

Concurrently switching neutral conductor
Yes
Additional equipment possible
Yes

Protection

Degree of protection (IP)
IP20
Explosion-proof
No

Operating conditions

Ambient temperature during operating
-30, 70 °C

Connection

Connectable conductor cross section multi-wired
1, 16 mm²
Connectable conductor cross section solid-core
1, 25 mm²

Logistics

Net weight
0.46 kg
Country of origin
France
Customs tariff number
8536201090

Packaging

PackQuantityGTINGross weightDimensions (L × W × D)
piece136064811693270.46 kg86.4 × 76.2 × 76.2 mm
box3136064811693241.428 kg230 × 80 × 90 mm
carton364360648116932517.623 kg400 × 300 × 300 mm

Documents