Skip to content
Eltracore

Schneider Electric

PowerPact-Multistandard, H-Rahmen, 100 A, 100 kA, Auslösegerät Micrologic 5.2 E

Manufacturer part no.
EAN
Price on requestAsk us for a quote for this product.
Checking availability…

Ordering

Order unit
piece

Description

PowerPact-Multistandard, H-Rahmen, 100 A, 100 kA, Auslösegerät Micrologic 5.2 E.

Technical data

ETIM class: Motor protection circuit-breaker (EC000074)

Electrical

Overload release current setting
35, 100.0 A
Adjustment range undelayed short-circuit release
150, 1500.0 A
Rated operating voltage
525, 525.0 V
Rated permanent current Iu
100 A
Rated operation power at AC-3, 230 V
UN kW
Rated operation power at AC-3, 400 V
UN kW
Power loss
UN W
With integrated under voltage release
Yes
Number of poles
3
Rated short-circuit breaking capacity Icu at 400 V, AC
65 kA

Model/type

With thermal overload protection
UN
Type of control element
Other
With integrated auxiliary switch
Yes

Options

Phase failure sensitive
Yes

Other

Switch off technique
Electronic
Device construction
Built-in device fixed built-in technique

Connection

Type of electrical connection of main circuit
Screw connection

Protection

Degree of protection (IP)
IP40

Measurements

Height
163 mm
Width
104 mm
Depth
86 mm

Logistics

Net weight
2.2 kg
Country of origin
United States
Customs tariff number
85362090

Packaging

PackQuantityGTINGross weightDimensions (L × W × D)
piece17859018303202.268 kg225 × 190 × 150.1 mm