Description
Special type Circuit breaker size S00 for motor protection CLASS 10 A-release 7...10 A N release 130 A Screw terminal Standard switching capacity with transverse auxiliary switch 1 NO+1 NC Ambient temperature -50 °C 500 switching cycles Simple, efficient and always up to date - SIRIUS modular system.
Technical data
ETIM class: Motor protection circuit-breaker (EC000074)
Electrical
- Overload release current setting
- 7, 10 A
- Adjustment range undelayed short-circuit release
- 130, 130 A
- Rated operating voltage
- 690, 690 V
- Rated permanent current Iu
- 10 A
- Rated operation power at AC-3, 230 V
- UN kW
- Rated operation power at AC-3, 400 V
- 4 kW
- Power loss
- 9.25 W
- With integrated under voltage release
- No
- Number of poles
- 3
- Rated short-circuit breaking capacity Icu at 400 V, AC
- 50 kA
Model/type
- With thermal overload protection
- UN
- Type of control element
- Other
- With integrated auxiliary switch
- Yes
Options
- Phase failure sensitive
- Yes
Other
- Switch off technique
- Magnetic
- Device construction
- Built-in device fixed built-in technique
Connection
- Type of electrical connection of main circuit
- Screw connection
Protection
- Degree of protection (IP)
- IP20
Measurements
- Height
- 90 mm
- Width
- 45 mm
- Depth
- 81 mm
Logistics
- Net weight
- 0.301 kg
- Country of origin
- Germany
- Customs tariff number
- 85362010
Packaging
| Pack | Quantity | GTIN | Gross weight | Dimensions (L × W × D) |
|---|---|---|---|---|
| packet | 1 | 4011209775954 | 0.301 kg | 100 × 49 × 84 mm |