Circuit breaker, for starter combination, rated current 20 A, short-circuit release 260 A
- Manufacturer part no.
- EAN
- Series
- SIRIUS 3RV2
Ordering
- Order unit
- piece
Description
Circuit breaker size S2 for starter combination Rated current 20 A N-release 260 A screw terminal Standard switching capacity Circuit breaker SIRIUS 3RV2 For starter combinations for the reliable protection of the loads in the event of a short-circuit and for the safe isolation from the network. Thanks to their low heat loss, these compact and climate-proof circuit breakers are optimized for use in load feeders, as well as for IE3/IE4 motors, of course. Worldwide approvals (e.g. IEC and UL/CSA) and applications in hazardous areas (ATEX or IEC Ex) are a matter of course. Device versions are available for motor protection (also with overload relay function), plant protection, short-circuit protection of starter combinations, transformer protection, as main and EMERGENCY OFF switches and for use in IT networks. They are available with screw or spring-type terminals for fast, maintenance-free and vibration-proof connection, and optionally with integral auxiliary switch. The comprehensive range of accessories, such as auxiliary switches, auxiliary releases, signaling switches etc. is standardized for all sizes. The use of different energy infeed options, such as the associated SIRIUS 3RV29 infeed system, considerably reduces the main circuit wiring. The 3RV2 circuit breakers replace the well-proven 3RV1 series. Simple, efficient and always up to date - SIRIUS modular system.
Technical data
ETIM class: Motor protection circuit-breaker (EC000074)
Electrical
- Overload release current setting
- UN A
- Adjustment range undelayed short-circuit release
- 260, 260 A
- Rated operating voltage
- 690, 690 V
- Rated permanent current Iu
- 20 A
- Rated operation power at AC-3, 230 V
- 5.5 kW
- Rated operation power at AC-3, 400 V
- 7.5 kW
- Power loss
- 14.5 W
- With integrated under voltage release
- No
- Number of poles
- 3
- Rated short-circuit breaking capacity Icu at 400 V, AC
- 65 kA
Model/type
- With thermal overload protection
- No
- Type of control element
- Other
- With integrated auxiliary switch
- No
Options
- Phase failure sensitive
- No
Other
- Switch off technique
- Magnetic
- Device construction
- Built-in device fixed built-in technique
Connection
- Type of electrical connection of main circuit
- Screw connection
Protection
- Degree of protection (IP)
- IP20
Measurements
- Height
- 140 mm
- Width
- 55 mm
- Depth
- 149 mm
Logistics
- Net weight
- 1.061 kg
- Country of origin
- Germany
- Customs tariff number
- 85362010
Packaging
| Pack | Quantity | GTIN | Gross weight | Dimensions (L × W × D) |
|---|---|---|---|---|
| packet | 1 | 4011209930285 | 1.061 kg | 147 × 62 × 167 mm |