Skip to content
Eltracore
No photo yet

Siemens

Digital monitoring relay voltage monitoring, 22.5 mm from 17 to 275 V AC/DC

Manufacturer part no.
EAN
Price on requestAsk us for a quote for this product.
Checking availability…

Ordering

Order unit
piece

Description

!!! product phase-out !!! the preferred successor is 3UG5643-2CS20 digital monitoring relay voltage monitoring, 22.5 mm from 17 to 275 V AC/DC overshoot and undershoot with internal power supply noise pulses delay 0.1 to 20 s hysteresis 0.1 to 150 V 1 changeover contact spring-loaded connection system Voltage monitoring relay with digital setting SIRIUS 3UG4 for monitoring voltages for overshooting and undershooting, e.g. for protecting a system from damage, for protecting batteries against deep discharge or for connecting systems as of a specified voltage. Worldwide use thanks to international certificates. The relay is variably adjustable to overshoot, undershoot or window monitoring. Delay times and RESET behavior are freely parameterizable. Less space required in the control cabinet thanks to slim design. Reliable diagnostics due to display of ACTUAL value and status messages. All versions with removable terminals. In addition to screw terminals, all the devices are also available with spring-type terminals for fast, maintenance-free and vibration-proof connection. The devices differ with regard to their power supply (internal or external), optionally with wide voltage range or with IO-Link. The comprehensive range of accessories, such as unit labeling plates, push-in lugs and cover caps, is standardized for all relays. SIRIUS relays - one range for every application.

Technical data

ETIM class: Voltage monitoring relay (EC001438)

Connection

Type of electric connection
Spring clamp connection
Number of contacts as normally closed contact
0
Number of contacts as normally open contact
0
Number of contacts as change-over contact
1

Model/type

With detachable clamps
Yes

Electrical

External power supply required
No
Voltage type (supply voltage)
AC/DC
Supply voltage AC 50 Hz
17, 275 V
Supply voltage AC 60 Hz
17, 275 V
Supply voltage DC
17, 275 V
Voltage measuring range 1
17, 275 V
Voltage measuring range 2
UN V
Type of voltage measuring range
AC/DC
Response value voltage
17, 275 V
Single-phase under voltage possible
Yes
Three-phase under voltage possible
No
Single-phase overvoltage possible
Yes
Three-phase overvoltage possible
No
Voltage type (operating voltage)
AC/DC
Operating voltage AC 50 Hz
240, 240 V
Operating voltage AC 60 Hz
240, 240 V
Operating voltage DC
24, 24 V
Rated switch current
3 A

Options

Single-phase hysteresis possible
Yes
Three-phase hysteresis possible
No
Contains function DC-under voltage
Yes
Contains function DC overvoltage
Yes
Contains function DC-voltage hysteresis
Yes

Setting/control

Min. adjustable delay-on energization time
0.1 s
Min. adjustable off-delay time
0.1 s

Operating conditions

Max. permitted delay-on energization time
20 s
Max. permitted off-delay time
20 s

Measurements

Width
22.5 mm
Height
94 mm
Depth
91 mm

Logistics

Net weight
0.13 kg
Country of origin
Germany
Customs tariff number
85364900

Packaging

PackQuantityGTINGross weightDimensions (L × W × D)
packet140112096427060.13 kg99 × 29 × 107 mm