!!! product phase-out !!! the preferred successor is 3UG5816-2AA40 line monitoring 3-phase+N digital monitoring relay for 3-phase voltage with N conductor for IO-Link 50...60 Hz AC 3 x 160 to 690 V phase sequence, phase failure phase asymmetry undervoltage and overvoltage hysteresis 1-20 V line stabilization delay tripping delay time 1 changeover contact, spring-loaded connection system Network monitoring relay with digital setting SIRIUS 3UG4 for monitoring phase sequence, phase failure and phase asymmetry as well as undervoltage and overvoltage, e.g. with unstable networks or mobile systems such as A/C compressors, refrigerated containers, construction site compressors or cranes. Worldwide use thanks to wide voltage supply range and international certificates. The relay is variably adjustable to overshoot, undershoot or window monitoring. Delay times and RESET behavior are freely parameterizable. Less space required in the control cabinet thanks to slim design. Reliable diagnostics due to display of the actual value and type of power system fault. All versions with removable terminals. In addition to screw terminals, all the devices are also available with spring-type terminals for fast, maintenance-free and vibration-proof connection. In addition, they are available in various voltages, and optionally with IO-Link or with automatic correction of the direction of rotation. The comprehensive range of accessories, such as unit labeling plates, push-in lugs and cover caps, is standardized for all relays. SIRIUS relays - one range for every application.

Technical data

ETIM class: Phase monitoring relay (EC001441)

Connection

Type of electric connection
Spring clamp connection
Number of contacts as normally closed contact
0
Number of contacts as normally open contact
0
Number of contacts as change-over contact
1

Model/type

With detachable clamps
Yes

Electrical

External power supply required
UN
Voltage type (supply voltage)
DC
Supply voltage AC 50 Hz
0, 0 V
Supply voltage AC 60 Hz
0, 0 V
Supply voltage DC
24, 24 V
Voltage measuring range
90, 400 V
Voltage type (operating voltage)
UN
Operating voltage AC 50 Hz
690, 690 V
Operating voltage AC 60 Hz
690, 690 V
Operating voltage DC
24, 24 V
Rated switch current
690 A

Options

Phase sequence monitoring
Yes
Phase failure detection
Yes
Function under voltage detection
Yes
Function overvoltage detection
Yes
Phase imbalance monitoring
Yes

Setting/control

Min. adjustable delay-on energization time
0 s
Min. adjustable off-delay time
0 s

Operating conditions

Max. permitted delay-on energization time
999.9 s
Max. permitted off-delay time
999.9 s

Measurements

Width
22.5 mm
Height
103 mm
Depth
91 mm

Logistics

Net weight
0.147 kg
Country of origin
Czechia
Customs tariff number
85364900

Packaging

PackQuantityGTINGross weightDimensions (L × W × D)
packet140112098957990.147 kg100 × 34 × 111 mm