circuit breaker 3VA1 IEC Frame 160 breaking capacity class H Icu=70 kA @ 415 V 3-pole, line protection TM240, ATAM, In=25 A overload protection Ir=...
- Manufacturer part no.
- EAN
- Series
- SENTRON 3VA1
Ordering
- Order unit
- piece
Description
circuit breaker 3VA1 IEC Frame 160 breaking capacity class H Icu=70 kA @ 415 V 3-pole, line protection TM240, ATAM, In=25 A overload protection Ir=18 A...25 A short-circuit protection Ii=6.4...12.8 x In nut keeper kit Molded case circuit breaker SENTRON 3VA1 for effective line protection with reliable disconnection in the event of overload and short-circuit. The 3VA molded case circuit breakers set new standards in flexibility and the variety of modular accessories available with a small space requirement. The 3VA1 molded case circuit breakers are available in 1-, 2-, 3-, and 4-pole versions with different rated uninterrupted currents for installation in fixed-mounted and plug-in/withdrawable versions. The modular and easy-to-install accessories with a wide range of functions are consistent and uniform for all sizes and series of 3VA molded case circuit breakers. SENTRON 3VA molded case circuit breakers - One system. For all applications.
Technical data
ETIM class: Power circuit-breaker for trafo/generator/installation protection (EC000228)
Electrical
- Rated permanent current Iu
- 25 A
- Rated voltage
- 690, 690 V
- Rated short-circuit breaking capacity Icu at 400 V, 50 Hz
- 70 kA
- Overload release current setting
- 17, 25 A
- Adjustment range short-term delayed short-circuit release
- UN A
- Adjustment range undelayed short-circuit release
- 160, 320 A
- Power loss
- 8.5 W
- With integrated under voltage release
- No
- Number of poles
- 3
Other
- Device construction
- Built-in device fixed built-in technique
Protection
- Integrated earth fault protection
- No
- Complete device with protection unit
- Yes
- Degree of protection (IP)
- IP40
Connection
- Type of electrical connection of main circuit
- Screw connection
- Number of auxiliary contacts as normally closed contact
- 0
- Number of auxiliary contacts as normally open contact
- 0
- Number of auxiliary contacts as change-over contact
- 0
- Position of connection for main current circuit
- Front side
Mounting/installation
- Suitable for DIN rail (top hat rail) mounting
- Yes
- DIN rail (top hat rail) mounting optional
- Yes
Model/type
- With switched-off indicator
- No
- Type of control element
- Rocker lever
- Motor drive integrated
- No
Options
- Motor drive optional
- Yes
Logistics
- Net weight
- 0.931 kg
- Country of origin
- Czechia
- Customs tariff number
- 85362010
Packaging
| Pack | Quantity | GTIN | Gross weight | Dimensions (L × W × D) |
|---|---|---|---|---|
| packet | 1 | 4042948808610 | 0.931 kg | 150 × 92 × 116 mm |