molded case switch 3VA5 UL Frame 250 max. short-circuit breaking capacity 65 kA @ 480 V 2-pole, line protection MCS110, In=250 A without overload p...
- Manufacturer part no.
- EAN
- Series
- SENTRON 3VA5
Ordering
- Order unit
- piece
Description
molded case switch 3VA5 UL Frame 250 max. short-circuit breaking capacity 65 kA @ 480 V 2-pole, line protection MCS110, In=250 A without overload protection intrinsic device protection Ii=10 x In without connection Molded-case circuit breaker SENTRON 3VA5 with UL approval as molded case switch. The 3VA5 and 3VA6 molded case circuit breakers set new standards in flexibility and the variety of modular accessories available with a small space requirement. In addition to the IEC standard, the two series also meet the UL standard. All of the functions can thus be used for plants around the world. The 3VA5 molded case circuit breakers are available in 2-, 3-, and 4-pole versions with different rated uninterrupted currents for installation in fixed-mounted versions. The modular and easy-to-install accessories with a wide range of functions are consistent and uniform for all sizes and series of 3VA molded case circuit breakers. SENTRON 3VA molded case circuit breakers - One system. For all applications.
Technical data
ETIM class: Power circuit-breaker for trafo/generator/installation protection (EC000228)
Electrical
- Rated permanent current Iu
- 250 A
- Rated voltage
- 690, 690 V
- Rated short-circuit breaking capacity Icu at 400 V, 50 Hz
- UN kA
- Overload release current setting
- UN A
- Adjustment range short-term delayed short-circuit release
- UN A
- Adjustment range undelayed short-circuit release
- 2500, 2500 A
- Power loss
- 36.26 W
- With integrated under voltage release
- No
- Number of poles
- 2
Other
- Device construction
- Built-in device fixed built-in technique
Protection
- Integrated earth fault protection
- No
- Complete device with protection unit
- Yes
- Degree of protection (IP)
- IP40
Connection
- Type of electrical connection of main circuit
- Other
- Number of auxiliary contacts as normally closed contact
- 0
- Number of auxiliary contacts as normally open contact
- 0
- Number of auxiliary contacts as change-over contact
- 0
- Position of connection for main current circuit
- Other
Mounting/installation
- Suitable for DIN rail (top hat rail) mounting
- No
- DIN rail (top hat rail) mounting optional
- No
Model/type
- With switched-off indicator
- No
- Type of control element
- Rocker lever
- Motor drive integrated
- No
Options
- Motor drive optional
- Yes
Logistics
- Net weight
- 1.9 kg
- Country of origin
- Czechia
- Customs tariff number
- 85362090
Packaging
| Pack | Quantity | GTIN | Gross weight | Dimensions (L × W × D) |
|---|---|---|---|---|
| packet | 1 | 4042948868324 | 1.9 kg | 245 × 150 × 160 mm |