SINAMICS PM240P-2, 3AC 380-480 V, 90,00 kW, IP20 / UL open type, FSF

Manufacturer part no.
EAN
Price on requestAsk us for a quote for this product.
Checking availability…

Ordering

Order unit
piece

Description

SINAMICS G120 POWER MODULE PM240P-2 UNFILTERED 3AC380-480V +10/-20% 47-63HZ OUTPUT HIGH OVERLOAD: 75KW FOR 150% 60S, 100% 240S; AMBIENT TEMP -20 TO +50 DEG C (HO) OUTPUT LOW OVERLOAD: 90kW FOR 135% 3S,110% 57S,100% 240S AMBIENT TEMP -20 TO +40 DEG C (LO) 708x 305x 357 (HXWXD), FSF PROTECTION IP20 WITHOUT CONTROL UNIT AND PANEL APPROVED FOR CU FIRMWARE- VERSION V4.7 SP6 HF1 Power Module SINAMICS PM240P-2 Power Module degree of protection IP20 for industrial applications in the process industries for the SINAMICS G120P frequency converter. The Power Modules are available for use in the water/waste water sector and for industrial applications. The new PM240P-2 Power Modules are based on a new hardware platform, which permits a higher power density. The PM240P-2 Power Modules are also suitable for use in safety-related applications. In conjunction with an external tripping unit (e.g. SIRIUS 3SK1), the drive becomes a Safety Integrated Drive with the safety function Safe Torque Off with a Safety Integrity Level of up to SIL 3. A further advantage of the Power Module is its ruggedness because it can also be used in severe ambient conditions, such as temperatures of -10° to 60° and in corrosive environments (resistance to pollution). Enhanced energy efficiency is also achieved with a higher output voltage (98 percent) due to an integrated DC link reactor. This Power Module does not contain an integrated braking chopper and the permissible cable lengths between the converter and the motor are limited. To permit longer cable lengths, output reactors can be connected. The PM240P-2 Power Modules in frame sizes FSD to FSF are available both with and without an integrated Class A line filter in a compact design in a three-phase voltage range of 380 V to 480 V and in a three-phase voltage range of 500 V to 690 V. The PM240P-2 Power Modules with an integrated Class A line filter are suitable for connection to TN systems. The Power Modules without an integrated line filter are suitable for connection to grounded TN/TT and ungrounded IT systems. Shield plates and shield connection kits are available for use when wiring the Control Units and Power Modules to ensure compliance with EMC guidelines. SINAMICS - simply my drive!

Technical data

ETIM class: Frequency converter =< 1 kV (EC001857)

Electrical

Mains voltage
380, 480 V
Mains frequency
UN
Max. output voltage
UN V
Nominal output current I2N
178 A
Power consumption
UN W
Relative symmetric net voltage tolerance
-10 %

Connection

Number of phases input
3
Number of phases output
3
Number of analogue outputs
UN
Number of analogue inputs
UN
Number of digital outputs
UN
Number of digital inputs
UN
With PC connection
UN

Other

Max. output frequency
550 Hz
Relative symmetric net frequency tolerance
5 %

Performance

Max. output at quadratic load at rated output voltage
90 kW
Max. output at linear load at rated output voltage
75 kW

Model/type

With control element
UN
Type of converter
U converter

Application

Application in industrial area permitted
No
Application in domestic- and commercial area permitted
No

Communication

Supporting protocol for TCP/IP
UN
Supporting protocol for PROFIBUS
UN
Supporting protocol for CAN
UN
Supporting protocol for INTERBUS
UN
Supporting protocol for ASI
UN
Supporting protocol for KNX
UN
Supporting protocol for Modbus
UN
Supporting protocol for Data-Highway
UN
Supporting protocol for DeviceNet
UN
Supporting protocol for SUCONET
UN
Supporting protocol for LON
UN
Supporting protocol for PROFINET IO
UN
Supporting protocol for PROFINET CBA
UN
Supporting protocol for SERCOS
UN
Supporting protocol for Foundation Fieldbus
UN
Supporting protocol for EtherNet/IP
UN
Supporting protocol for AS-Interface Safety at Work
UN
Supporting protocol for DeviceNet Safety
UN
Supporting protocol for INTERBUS-Safety
UN
Supporting protocol for PROFIsafe
UN
Supporting protocol for SafetyBUS p
UN
Supporting protocol for BACnet
UN
Supporting protocol for other bus systems
UN
Number of HW-interfaces industrial Ethernet
UN
Number of interfaces PROFINET
UN
Number of HW-interfaces RS-232
UN
Number of HW-interfaces RS-422
UN
Number of HW-interfaces RS-485
UN
Number of HW-interfaces serial TTY
UN
Number of HW-interfaces USB
UN
Number of HW-interfaces parallel
UN
Number of HW-interfaces other
UN
With optical interface
UN

Options

Integrated breaking resistance
No

Setting/control

4-quadrant operation possible
No

Protection

Degree of protection (IP)
UN
Degree of protection (NEMA)
UN

Measurements

Height
708 mm
Width
305 mm
Depth
357 mm

Logistics

Net weight
58 kg
Country of origin
Germany
Customs tariff number
85044086

Packaging

PackQuantityGTINGross weightDimensions (L × W × D)
packet1404294867349271 kg745 × 469 × 385 mm