Photo 1 of 3
Surge suppression module for signal technology;Nominal voltage: 24 VDC;for 2 signal paths with common surge arrester
- Manufacturer part no.
- EAN
- Series
- 792 Series
Price on requestAsk us for a quote for this product.
Ordering
- Order unit
- piece
Description
Surge suppression module for signal technology; Nominal voltage: 24 VDC; for 2 signal paths with common surge arrester; for supply lines; Single-stage; Width: 6 mm; 2,50 mm²
Technical data
ETIM class: Surge protection device for data networks/MCR-technology (EC000943)
Electrical
- Nominal voltage AC
- -, - V
- Nominal voltage DC
- 24, 24 V
- Max. continuous voltage AC
- 23 V
- Max. continuous voltage DC
- 33 V
- Nominal discharge surge current (8/20)
- 5 kA
- Lightning impulse current (10/350 µs)
- - kA
- Nominal load current
- 10 A
- Voltage protection level core/core
- 50 V
- Voltage protection level core/earth
- 750 V
- Voltage protection level core/signal ground
- - V
- Voltage protection level signal ground/protective ground
- - V
- Number of conductors (without earthing)
- 2
Other
- Frequency
- -, - MHz
- Limiting frequency
- 6 MHz
- Signalling at the device
- None
- Earthing via
- -
Mounting/installation
- Mounting method
- DIN rail (top hat rail) 35 mm
Connection
- Connection 1
- Clamp
- Signal disconnection
- -
Setting/control
- Pro-active thermo-control
- No
Communication
- With remote signalling contact
- No
Protection
- Explosion-tested version
- No
- Degree of protection (IP)
- -
Measurements
- Assembly width
- 6 mm
Logistics
- Country of origin
- Germany
- Customs tariff number
- 85363010
Packaging
| Pack | Quantity | GTIN | Gross weight | Dimensions (L × W × D) |
|---|---|---|---|---|
| carton | 1 | — | 0.037 kg | 105 × 75 × 20 mm |