Skip to content
Eltracore

Photo 1 of 3

Doepke

Residual current monitor Type A, 85V - 264V AC

Manufacturer part no.
EAN
Price on requestAsk us for a quote for this product.
Checking availability…

Ordering

Order unit
piece

Description

Residual current monitors (RCM) reliably detect and report fault and differential currents without switching off the system. They are used wherever the system cannot be switched off, or this is not desired. Series DRCM residual current monitors These devices provide a quick overview of the system status. The current residual current is displayed by means of a bar graph indicator. The 10-segment LED display on the front of the device indicates when the response thresholds are exceeded. If alarm signaling is required, external signaling devices can be connected. The devices feature an adjustable response delay, which prevents unwanted signaling caused by short-term residual current impulses (e.g. due to thunderstorms or switching overvoltages). Optimal system integration is ensured by a wide range of compatible summation current transformers for different conductor cross-sections and corresponding rated currents. Monitors with residual current characteristic A detect sinusoidal AC currents as well as pulsating DC residual currents. Standard RCCBs are designed for circuits with 230/400 V at 50 Hz.

Tender text

Pulsstromsensitives Differenzstrom-Überwachungsgerät RCM Typ A nach DIN EN 62020 im Bereich 50 Hz - 60 Hz. Ansprechdifferenzstromcharakteristik: A Selektivität einstellbar: true max. einstellbarer Ansprechdifferenzstrom I∆adj AC: 0.03 A, 0.1 A, 0.3 A, 1 A, 3 A Frequenzbereich Fehleransprechstrom Typ A: 50 Hz ... 60 Hz Frequenzbereich Fehleransprechstrom Typ AC: 50 Hz ... 60 Hz Frequenzbereich Ansprechdifferenzstrom Typ A: 50 Hz ... 60 Hz Frequenzbereich Ansprechdifferenzstrom Typ AC: 50 Hz ... 60 Hz Spannungsart des überwachten Stromkreises: AC Bemessungsspannungsbereich Uem des überwachten Stromkreises AC: 0 V ... 690 V Bemessungsfrequenzbereich des überwachten Stromkreises: 50 Hz ... 60 Hz Einstellwerte Verzögerung bei I∆n = 30 mA: 0.1 s, 0.2 s, 0.3 s, 0.4 s, 0.5 s, 0.6 s, 0.7 s, 0.8 s, 0.9 s, 1 s Einstellwerte Verzögerung bei I∆n ≥ 100 mA: 0.1 s, 0.2 s, 0.3 s, 0.4 s, 0.5 s, 0.6 s, 0.7 s, 0.8 s, 0.9 s, 1 s Wandler extern: DCT A-20, DCT A-30, DCT A-35, DCT A-70, DCT A-105, DCT A-140, DCT A-210 Fehlerspeicher vorhanden Bedienelemente: Bereichsschalter für Ansprechdifferenzstrom, Bereichsschalter für Voralarmschwelle, Bereichsschalter für Grenznichtansprechzeit, Rücksetztaster, Testtaste Voralarmausgang (Relais): 1 Wechsler Polzahl (gesamt): 2 Bemessungsspannung (AC): 230 V Bemessungsstrom AC (typ.): 5 A Bemessungsfrequenz: 50 Hz ... 60 Hz Hauptalarmausgang (Relais): 1 Wechsler Bemessungsspannung (AC): 230 V Bemessungsstrom AC (typ.): 5 A Bemessungsfrequenz: 50 Hz ... 60 Hz Betriebsspannung (AC): 230 V (85 V ... 264 V) Betriebsfrequenz: 50 Hz, 60 Hz Gehäuseart: Verteilereinbaugehäuse Montageart: Tragschiene (35 mm) Schutzart: IP40 Abmessungen: B 71,6 mm (4 TE) × H 89,7 mm × T 62,2 mm Außendurchmesser: 1.5 mm Bauvorschriften/Normen: EN 62020, EN 60044 Fabrikat: Doepke oder gleichwertig Artikelbezeichnung: DRCM 1 A Bestellnummer: 09340250 gewähltes Fabrikat/Typ: ___________/___________

Technical data

ETIM class: Residual current monitoring relay (EC001445)

Connection

Type of electric connection
Screw connection
Number of contacts as normally closed contact
0
Number of contacts as normally open contact
0
Number of contacts as change-over contact
1

Model/type

With detachable clamps
No
Function
For AC-current system

Electrical

External power supply required
Yes
Voltage type (supply voltage)
AC
Supply voltage AC 50 Hz
230, 230 V
Supply voltage AC 60 Hz
85, 264 V
Supply voltage DC
UN V
Voltage measuring range
0, 690 V
Current measuring range
UN mA
Response value amperage 1
30, 3000 mA
Response value amperage 2
UN mA
Voltage type (operating voltage)
AC
Operating voltage AC 50 Hz
230, 230 V
Operating voltage AC 60 Hz
85, 264 V
Operating voltage DC
UN V
Rated switch current
5 A

Other

Rated operating frequency
50, 60 Hz

Setting/control

Min. adjustable delay-on energization time
0.1 s

Operating conditions

Max. permitted delay-on energization time
1 s

Options

Indication of difference current
Yes
Error registration possible
Yes

Measurements

Width
71.6 mm
Height
89.7 mm
Depth
62.2 mm

Logistics

Net weight
0.218 kg
Country of origin
Germany
Customs tariff number
90303370

Packaging

PackQuantityGTINGross weightDimensions (L × W × D)
carton140147121995380.218 kg110 × 90 × 80 mm